SiUS372201EB
[2-29]:
[2-30]:
[2-31]:
Part 5 Field Settings and Test Operation
Intermittent fan operation
Used for intermittent fan operation to assist snow discharge on outdoor fan.
Default value: 0.
Value
[2-29]
0 (default)
1
30 minutes OFF, 1 minute ON with medium fan speed
2
30 minutes OFF, 1 minute ON with high fan speed
3
15 minutes OFF, 1 minute ON with medium fan speed
4
15 minutes OFF, 1 minute ON with high fan speed
5
5 minutes OFF, 1 minute ON with medium fan speed
6
5 minutes OFF, 1 minute ON with high fan speed
7
Continuously ON with medium fan speed
Power consumption limitation level (step 1) via the external control adaptor
(DTA104A62)
If the system needs to run under power consumption limitation conditions when an
external signal is sent to the unit, this setting defines the level power consumption
limitation that will be applied for step 1. The level is according to the table.
Default value: 3
Change [2-30]: 1, 2, 3, 4, 5, 6, 7, or 8 in function of required limitation
Value
Power consumption limitation (Approximate)
[2-30]
1
2
3 (default)
4
5
6
7
8
Power consumption limitation level (step 2) via the external control adaptor
(DTA104A62)
If the system needs to run under power consumption limitation conditions when an
external signal is sent to the unit, this setting defines the level power consumption
limitation that will be applied for step 2. The level is according to the table.
Default value: 1
Change [2-31] to 1, 2 or 3 in function of required limitation.
Value
Power consumption limitation (approximately)
[2-31]
1 (default)
2
3
Intermittent fan operation
OFF
60%
65%
70%
75%
80%
85%
90%
95%
40%
50%
55%