Cool/Heat Mode Changeover
Set Cool/Heat Separately for Each Branch Selector Unit by Cool/Heat Selector.
Set remote controller changeover switch DS1-1 as following:
Set the DIP switch (DS1-1) on printed circuit board (A1P) as shown below before turning on the
When using cool/heat selector, connect to the terminal A, B and C on the PCB of the electrical
component box.
EXAMPLE OF TRANSMISSION LINE CONNECTION
Example of connecting transmission wiring.
Connect the transmission wirings as shown in the figure below.
Outdoor unit
TO IN/D UNIT TO OUT/D UNIT
F1 F2
F1 F2
A
B
F1
F2
F1
F2
IN/D
OUT/D.BS
C
Branch Selector unit A
F1
F2
F2
F1
Part 5 Field Settings and Test Operation
power to the Branch Selector unit.
In case of the indoor unit connect as the cooling only unit, it wire
the terminal
F1
IN/D
To the indoor unit where
the selection of heating
and cooling is available.
Branch wiring
Use 2-core wires.
(There is no polarity.)
F1
F2
F1
F2
OUT/D.BS
IN/D
Branch Selector unit B
F1
F2
COOL/HEAT
selector
ON
Turn on DS1-1.
OFF 1
of the last Branch Selector unit.
F1
F2
OUT/D.BS
F2
F1
F2
F1 F2
OUT/D.BS
Final Branch
Selector unit
1st unit
Cool/heat selector remote
control wiring
Use 3-core wires.
(Keep in mind the polarity.)