Outline of Control (Indoor Unit)
9.4.3 Thermostat Control with Operation Mode Set to AUTO
The system will conduct this temperature control shown below, only when the wireless remote
controller or any central remote controller is connected.
Furthermore, setting changes of the differential value (D) can be made.
Mode
First code
No.
No.
12
4
Automatic mode differential
(22)
Heating thermostat OFF
Heating thermostat ON
187
Contents of setting
Set heating temperature
(A – D)
Display change
Cooling o Heating
3qC (5.4qF)
(Ex.) When automatic cooling temperature is set to 27qC (80.6qF):
Differential value: 0qC (0qF)
Set cooling/ heating temp.
30qC
25qC
27qC
(86qF)
(77qF)
(80.6qF)
Control temp.
Heating mode
Differential value set to 1qC (1.8qF)
Set heating temp. Set cooling temp.
26qC
27qC
29qC
(78.8qF)
(80.6qF)
(84.2qF)
24.5qC
(76.1qF)
Control temp.
Heating mode
Differential value set to 2qC (3.6qF)
Set heating temp. Set cooling temp.
25qC
27qC
28qC
(77qF)
(80.6qF)
(82.4qF)
24qC
(75.2qF)
Control temp.
Heating mode
Differential value set to 3qC (5.4qF)
Set heating temp. Set cooling temp.
24qC
27qC
(75.2qF)
(80.6qF)
23.5qC
(74.3qF)
Control temp.
Heating mode
01
02
03
0°C
1°C
2°C
0°F
1.8°F
3.6°F
Set cooling temperature
A
D
Display change
Heating o Cooling
D
(
+ 2)qC
2
D
(
+ 3.6)qF
2
Differential value set to 4qC (7.2qF)
Set heating temp.
23qC
(73.4qF)
Cooling mode
Heating mode
Differential value set to 5qC (9qF)
Set heating temp.
22qC
22.5qC
Cooling
(71.6qF)
(72.5qF)
mode
Heating mode
Differential value set to 6qC (10.8qF)
Set heating
temp.
22qC
Cooling
(71.6qF)
(75.2qF)
21qC
mode
(69.8qF)
Heating mode
Differential value set to 7qC (12.6qF)
Set heating
temp.
21.5qC
(70.7qF)
(73.4qF)
Cooling mode
20qC
(68qF)
Heating mode
Second code No.
04
05
06
3°C
4°C
5°C
5.4°F
7.2°F
9.0°F
Cooling thermostat ON
Cooling thermostat OFF
Set cooling temp.
26qC
27qC
(78.8qF)
(80.6qF)
Cooling mode
Control temp.
Set cooling temp.
25qC
27qC
(77qF)
(80.6qF)
Cooling mode
Control temp.
Set cooling temp.
24qC
27qC
(80.6qF)
Cooling mode
Control temp.
Set cooling temp.
23qC
27qC
(80.6qF)
Cooling mode
Control temp.
Part 4 Functions and Control
SiUS372201EB
: Factory setting
07
08
6°C
7°C
10.8°F
12.6°F

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv emerion reyq-aatjbVrv emerion reyq-aaydaVrv emerion reyq-aaydbVrv emerion reyq72aatjaVrv emerion reyq72aaydbVrv emerion reyq72aatjb ... Show all

Table of Contents