Troubleshooting by Error Code
1. Check also if the relay connector between the indoor unit control PCB and the fan motor are
correctly connected.
Reference
CHECK 16 Refer to page 466.
321
A
The HAP
lamp on the indoor unit
control PCB is
blinking.
YES
NO
SiUS372201EB
Replace the indoor unit control
PCB (A1P).
Replace the fan motor (M1F).