Field Settings for Indoor Unit
1.4.24 Swing Pattern Settings (For units with the infrared floor sensor only)
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed side
by side are set to swing in an opposite direction to agitate airflow to reduce temperature irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
Mode
13 (23)
1.4.25 Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
Mode
13 (23)
Note(s)
When the model FXFQ-AA is attached with a closing member kit, set the Second Code No. to 02 or
03.
1.4.26 Setting of Static Pressure Selection
FXDQ-M
Mode No.
FXMQ-TA
Mode No.
229
First Code
Second Code
No.
No.
No.
01
2
02
03
First Code
Second Code
No.
No.
No.
01
4
02
03
First Code No.
13 (23)
5
First Code No.
13 (23)
5
All direction synchronized swing
Ceiling soiling prevention (Downward)
Second Code No.
Standard (FXDQ07-12M: 10 Pa (0.04 inWG),
01
High static pressure (FXDQ07-12M: 15 Pa (0.06 inWG),
02
Second Code No.
01
02
03
: Factory setting
Contents
—
Facing swing
: Factory setting
Contents
Draft prevention (Upward)
Standard
: Factory setting
Contents
FXDQ18/24M: 30 Pa (0.12 inWG))
FXDQ18/24M: 45 Pa (0.18 inWG))
: Factory setting
Contents
Standard
Level 1
Level 2
Part 5 Field Settings and Test Operation
SiUS372201EB