Electronic Expansion Valve Pi Control; Step Control Of Outdoor Unit Fans - Daikin VRV III REYQ8PY1B Service Manual

R-410a heat recovery 50hz
Hide thumbs Also See for VRV III REYQ8PY1B:
Table of Contents

Advertisement

Basic Control
2.3

Electronic Expansion Valve PI Control

Main electronic expansion valve EVM control
When the outdoor unit heat exchanging is performed via the evaporator (20SA is set to ON),
this function is used to exert PI control on the electronic expansion valve (Y1E or Y3E) so that
the evaporator outlet superheated degree (SH) will become constant.
SH = Tg - Te
Subcooling electronic expansion valve EVT control
In order to make the maximum use of the subcool heat exchanger, this function is used to exert
PI control on the electronic expansion valve (Y2E, Y5E or Y3E) so that the evaporator-side gas
pipe superheated degree (SH) will become constant.
SH = Tsh - Te
Refrigerant charge electronic expansion valve EVJ control
While in automatic refrigerant charge mode, this function is used to exert PI control on the
opening degree of the electronic expansion valve (Y2E or Y4E) in response to outdoor
temperature and close the valve after the completion of refrigerant charge.
For normal operation, fully open this electronic expansion valve.
2.4

Step Control of Outdoor Unit Fans

Used to control the revolutions of outdoor unit fans in the steps listed in table below, according to condition changes.
STEP No.
8HP
10HP
0
0
1
285/255
285/255
2
315/285
315/285
3
360/330
360/330
4
430/400
430/400
5
590/560
590/560
6
690/660
690/660
7
820/790
820/790
8
920/890
920/890
9
920/890
920/890
Fan1/Fan2 Fan1/Fan2 Fan1/Fan2 Fan1/Fan2 Fan1/Fan2
* Figures listed above are all those controlled while in standard mode, which vary when the system is set to high static
pressure or capacity precedence mode.
114
Single type
12HP
14HP
0
0
0
285/255
285/255
315/285
360/315
360/330
395/365
430/400
480/440
590/560
560/530
690/660
760/730
820/790
960/930
951/931
1125/1095 1155/1125
1020/990 1125/1095 1200/1170
SH: Evaporator outlet superheated degree
(°C)
Tg : Suction pipe temperature (°C) detected
by the heat exchanger gas pipe
thermistor R2T.
Te : Low pressure equivalent saturated
temperature (°C)
SH: Evaporator outlet superheated degree
(°C)
Tsh:Suction pipe temperature (°C) detected
by the subcool heat exchanger outlet
thermistor R5T
Te: Low pressure equivalent saturated
temperature (°C)
Fan revolutions (rpm)
16HP
M8
M10
0
0
285/255
350
350
360/315
370
370
395/365
400
400
480/440
450
450
560/530
540
560
760/730
610
680
960/930
680
710
710
750
796
821
Multiple type
M12
M14
0
0
0/0
350
230/0
370
380/0
400
290/260
450
375/345
560
570/540
680
720/690
710
910/880
775
1091/1061 1091/1061
870
1136/1106 1136/1106
Fan1/Fan2 Fan1/Fan2
SiBE37-701
M16
0/0
230/0
380/0
290/260
375/345
570/540
720/690
910/880
Function