SiUS372201EB
2.5.2 Overview of Setting Mode (Mode 2)
This overview shows the available settings by using the press buttons on the outdoor unit PCB.
No.
Item
1
COOL/HEAT
Several systems as 1 zone change
selection
over COOL/HEAT:
 INDIVIDUAL: VRV indoor unit or
A-B-C input set mode.
0
 MASTER: System is the
COOL/HEAT master unit.
 SUB: System is not a
COOL/HEAT master.
Low noise/
Used to make address setting for
2
demand address
low noise/demand operation.
Indoor fan forced
Used to force the fan of indoor unit
5
H
to H tap.
Forced
Used to force all indoor units to
6
thermostat
operate forced thermostat ON.
Eco level setting
Used to make setting of Eco level
for Eco mode via
for Eco mode via External control
7
External control
adaptor
adaptor
Te setting
Used to make setting of targeted
evaporating temperature for
cooling operation.
8
Tc setting
Used to make setting of targeted
condensing temperature for
9
heating operation.
The heating
Used for heating capacity cut offset
capacity cut
temperature setting.
10
offset
temperature
setting
External low
Used to receive external low noise
12
noise setting/
or demand signal.
demand setting
AIRNET address Used to set address of AIRNET.
13
Heat pump
Used for heat pump lockout.
16
lockout 1
High ESP setting
Fan high static pressure setting
18
FAN
Phased
Used to make setting for phased
19
installation
installation.
setting
Additional
Used to perform additional
refrigerant
refrigerant charging operation
charge/Wrong
(compressor operation) and wrong
20
wiring automatic
wiring automatic detection for
detection for
Branch Selector.
Branch Selector
Refrigerant
Used to set the system to
21
recovery and
refrigerant recovery mode (without
vacuuming
compressor run).
Automatic night-
Automatic night-time low noise
time low noise
operation.
22
operation
Time for the operation is subject to
the start and end time settings.
Part 5 Field Settings and Test Operation
Description
SEG
1
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
7 segment
display
Description
SEG
SEG
2
3
Individual
Unified Master
Unified Sub
0
0
Address:
0
2
0 ~
31
Normal operation
0
5
Indoor fan H
Normal operation
0
6
Forced thermostat ON
Inactive
Eco mode active by low noise
0
7
terminal short-circuit
Eco mode active by demand
terminal short-circuit
Auto
6°C (42.8°F)
7°C (44.6°F)
0
8
8°C (46.4°F)
9°C (48.2°F)
10°C (50.0°F)
11°C (51.8°F)
Auto
41°C (105.8°F)
0
9
43°C (109.4°F)
46°C (114.8°F)
Default 2.0°C (3.6°F)
1.0°C (1.8°F)
1
0
0.5°C (0.9°F)
Input LNO/DE
1
2
OFF
ON
Address:
1
3
0 ~
63
OFF
1
6
ON
OFF
1
8
ON
Normal installation
1
9
Single module to dual module
installation
OFF
Refrigerant charging ON
Wrong wiring automatic
2
0
detection ON
Refrigerant recovery
OFF
2
1
ON
OFF
Level 1
2
2
Level 2
Level 3
Field Setting from Outdoor Unit
7 segment
display
Range
SEG
SEG
1
2
3
6
SEG
3
0
1
2
0
1
0
1
0
1
0
1
2
0
2
3
4
5
6
7
0
1
3
6
0
1
2
0
1
0
3
0
1
0
1
0
1
0
1
2
0
1
0
1
2
3
248