Daikin VRV EMERION REYQ-AATJA Service Manual page 271

Table of Contents

Advertisement

SiUS372201EB
[2-81]:
Change [2-81] to 0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-8] and [2-47].
In the case [2-81] is 0, the original refrigerant temperature target based on [2-8] and [2-47] is kept
without any correction, unless for protection control.
For more information and advice about the effect of these settings, refer to Energy Saving and
Optimum Operation on page 276.
[2-82]:
Change [2-82] to 0, 1, 2 or 3 in function of required limitation.
This setting is used in conjunction with setting [2-9].
In the case [2-82] is 0, the original refrigerant temperature target based on [2-9] is kept without any
correction, unless for protection control.
For more information and advice about the effect of these settings, refer to Energy Saving and
Optimum Operation on page 276.
[2-89]:
Note(s)
Setting [2-89] to 2 saves energy, but the time to reach the set point may be longer.
Part 5 Field Settings and Test Operation
Cooling comfort setting for VRT control
Default value: 1
Value
[2-81]
0
1 (default)
2
3
Heating comfort setting for VRT control
Default value: 1.
Value
[2-82]
0
1 (default)
2
3
Optional setting to prioritize VRT control
Default value: 0.
Value
[2-89]
0 (default)
2
Cooling comfort setting
Eco
Mild
Quick
Powerful
Heating comfort setting
Eco
Mild
Quick
Powerful
Level
Prioritize largest demand
Prioritize smallest demand
Field Setting from Outdoor Unit
264