Field Setting from Outdoor Unit
No.
Item
1
Te setting (Heat
Used to make setting of targeted
recovery
evaporating temperature for heat
operation)
recovery operation.
47
Outdoor > 50 m
Height difference setting max. 110
49
(164 ft) above
m (361 ft).
indoor
Sequence multi
Sequence addressing between
51
outdoor
master and sub units.
Gas furnace
Used for gas furnace connection
60
setting
Cooling/Heating
Adjust cooling and heating capacity
capacity learning
learning control
62
control
Eco mode
Used to make setting of Eco mode
invalid setting
invalid
When this configuration is set, it is
64
not possible to turn Eco mode
ON/OFF using external control
adaptor or other setting.
Branch selector
Used for changing branch selector
switching time
switching time
71
All piping length between branch
selector unit and indoor units
should be less than 9.7 m (32 ft).
Heat pump
Heat pump is locked out when the
lockout
outdoor air temperature is smaller
temperature
than the heat pump lockout
temperature.
78
Heat pump
Heat pump would be resumed
lockout release
when the outdoor air temperature
79
differential
is recovered by differential above
the heat pump lockout
temperature.
Cooling comfort
Cooling comfort setting for VRT
setting
control
81
Heating comfort
Heating comfort setting for VRT
setting
control
82
Optional setting
If indoor units are located
to prioritize VRT
throughout multiple spaces with
control
different set points, it is
89
recommended to keep this setting
to 0. If all indoor units are located in
the same space, the setting of 2
saves energy.
251
Description
SEG
1
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
2.
7 segment
display
Description
SEG
SEG
2
3
Auto
6°C (42.8°F)
7°C (44.6°F)
4
7
8°C (46.4°F)
9°C (48.2°F)
10°C (50.0°F)
11°C (51.8°F)
Off (max. 50 m (164 ft))
4
9
On (max 110 m (361 ft))
Automatic
5
1
Forced master
Forced sub
No gas furnace connection
6
0
Gas furnace connection
OFF
Cooling adjustment
6
2
Heating adjustment
Cooling and heating
adjustment
Activated both cooling and
heating
Activated heating only
6
4
Activated cooling only
Deactivated
Standard
Approximately 4 minutes
7
1
–26.1°C (–15°F)
–23.3°C (–10°F)
–20.5°C (–5°F)
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
7
8
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
Forced heat pump lockout
2.8°C (5°F)
5.6°C (10°F)
7
9
8.3°C (15°F)
Eco
Mild
8
1
Quick
Powerful
Eco
Mild
8
2
Quick
Powerful
Prioritize largest demand
Prioritize smallest demand
8
9
Part 5 Field Settings and Test Operation
SiUS372201EB
7 segment
display
Range
SEG
SEG
SEG
1
2
3
0
2
3
4
5
6
7
0
1
0
1
2
0
1
0
1
2
3
0
1
2
3
0
1
0
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
1
4
0
1
2
0
1
2
3
0
1
2
3
0
2