Part 5 Field Settings and Test Operation
shows the status of night-time low noise operation.
 0: unit is currently not operating under low noise restrictions
 1: unit is currently operating under low noise restrictions
Night-time low noise operation reduces the sound generated by the unit compared to
nominal operating conditions.
Night-time low noise operation can be set in mode 2. There are two methods to activate
night-time low noise operation of the outdoor unit system.
The first method is to enable an automatic night-time low noise operation by field
setting. The unit will operate at the selected low noise level during the selected time
frames.
The second method is to enable night-time low noise operation based on an external
input. For this operation an optional accessory is required.
shows the status of power consumption limitation operation.
 0: unit is currently not operating under power consumption limitations
 1: unit is currently operating under power consumption limitation
Power consumption limitation reduces the power consumption of the unit compared to
nominal operating conditions.
Power consumption limitation can be set in mode 2.
There are two methods to activate power consumption limitation of the outdoor unit
system.
The first method is to enable a forced power consumption limitation by field setting. The
unit will always operate at the selected power consumption limitation.
The second method is to enable power consumption limitation based on an external
input. For this operation an optional accessory is required.
shows the current Te target parameter position.
shows the current Tc target parameter position.
shows the AIRNET address.
shows the total number of connected indoor units.
It can be convenient to check if the total number of indoor units which are installed
match the total number of indoor units which are recognized by the system. In case
there is a mismatch, it is advised to check the communication wiring path between
outdoor and indoor units (F1/F2 communication line).
shows the total number of connected Branch Selector units.
Check if the total number of installed Branch Selector units match the total number of
Branch Selector units recognized by the system. In case there is a mismatch, check the
communication wiring path between outdoor and Branch Selector units (F1/F2
communication line).
For the Multi Branch Selector unit, the number of units in use is counted.
shows the total number of connected outdoor units.
It can be convenient to check if the total number of outdoor units which are installed
matches the total number of outdoor units which are recognized by the system. In case
there is a mismatch, it is advised to check the communication wiring path between
outdoor and outdoor units.
shows the latest error code.
shows the 2nd last error code.
shows the 3rd last error code.
When the latest error codes were reset by accident on an indoor unit user interface,
they can be checked again through this monitoring settings.
shows the latest prediction code.