3.48 Branch Selector Unit Electronic Expansion Valve
Abnormality
Applicable
Branch Selector unit
Models
F9
Error Code
Method of Error
The error is detected by whether or not all coils of the electronic expansion valve have continuity.
Detection
Error Decision
The power supply turns ON, but there is no currents pass through the common (COM[+]).
Conditions
Supposed
 Disconnection of the electronic expansion valve connector
Causes
 Defective electronic expansion valve coil
 Defective PCB of Branch Selector unit
Troubleshooting
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn power supply OFF, and
turn power supply ON again.
Return to normal?
NO
While in monitor mode,
identify an electronic
expansion valve subject to
the Error Code F9. ( 1)
The connector
of outdoor unit main PCB
for electronic expansion
valve is connected.
YES
Identify the electronic
expansion valve coil to be
checked based on the table.
( 2)
The coil
resistance of electronic
expansion valve is normal.
CHECK 18
YES
YES
NO
NO
Troubleshooting by Error Code
External factor other than
error (for example, noise
etc.).
Ensure the correct
connection.
Replace the electronic
expansion valve coil.
Replace the Branch
Selector unit PCB.
388