SiUS372201EB
[2-38]:
[2-39]:
[2-42]:
[2-45]:
This setting is not applicable to BS-Q54TVJ models.
[2-47]:
Change [2-47] to 0, 2-7 in function of required operation method during heat recovery operation.
For more information and advice about the effect of these settings, see Energy Saving and
Optimum Operation on page 276.
Part 5 Field Settings and Test Operation
Emergency operation Master
To disable compressor operation permanently: in case of single module or Master unit
of a multi outdoor system, this setting allows:
Default value: 0. Compressor operation enabled.
Field setting:
 Set 1: Master INV. 1 is disabled permanently.
 Set 2: Master INV. 2 is disabled permanently
 Set 3: Master module is disabled permanently.
Emergency operation Sub
To disable compressor operation of Sub unit of a multi outdoor system permanently:
Default value: 0. Compressor operation enabled.
Field setting:
 Set 1: Sub INV. 1 is disabled permanently.
 Set 2: Sub INV. 2 is disabled permanently
 Set 3: Sub module is disabled permanently.
Outdoor fan noise countermeasure
Change fans rotational speed and reduce noise by the interference of air blow noise
between outdoor units.
Default value: 0
Field setting:
 Mode A: 1
 Mode B: 2
Low ambient cooling
Default value: 0.
[2-45]
0 (default)
1
Te target temperature during heat recovery operation
Default value: 2.
Value
[2-47]
0
2 (default)
3
4
5
6
7
Description
No low ambient cooling available.
Low ambient cooling available.
Te target
Auto
6°C (42.8°F)
7°C (44.6°F)
8°C (46.4°F)
9°C (48.2°F)
10°C (50.0°F)
11°C (51.8°F)
Field Setting from Outdoor Unit
262