Field Setting from Outdoor Unit
2.7.3 Setting Procedure of Night-Time Low Noise Operation and Demand
Operation
1. Setting mode 1 (H1P OFF)
In setting mode 2, press the MODE (BS1) button once  Setting mode 1 is entered and H1P turns
OFF. While the setting mode 1 is displayed, In night-time low noise operation and In demand
operation are displayed.
2. Setting mode 2 (H1P ON)
1. In setting 1, press and hold the MODE (BS1) button for more than 5 seconds.  Setting mode 2
2. Press the SET (BS2) button several times and match the LED display with the Setting No. you
3. Press the RETURN (BS3) button once, and the present setting content is displayed.  Press
4. Press the RETURN (BS3) button two times.  Returns to (1).
5. Press the MODE (BS1) button once  Returns to the setting mode 1 and H1P turns OFF.
275
is entered and H1P lights.
want.
the SET (BS2) button several times and match the LED display with the setting content you
want.
SiUS372201EB