Daikin VRV EMERION REYQ-AATJA Service Manual page 285

Table of Contents

Advertisement

SiUS372201EB
temporary base depending on the situation.
In case of heating operation the condense temperature is allowed to go up to 115°F (46°C) on
temporary base depending on the situation.
When the request from the indoor units becomes more moderate, the system will eventually go to
the steady state condition which is defined by the operation method above.
The start up condition is different from the powerful and quick comfort setting.
 To activate the mild comfort setting under cooling operation, change field setting [2-81] to 1.
 To activate the mild comfort setting under heating operation, change field setting [2-82] to 1.
• Eco
The original refrigerant temperature target, which is defined by the operation method (see above) is
kept without any correction, unless for protection control.
 To activate the eco comfort setting under cooling operation, change field setting [2-81] to 0.
 To activate the eco comfort setting under heating operation, change field setting [2-82] to 0.
No matter which control is selected, variations on the behavior of the system are still possible due
to protection controls to keep the unit operating under reliable conditions. The intentional target,
however, is fixed and will used to obtain the best balance between energy consumption and
comfort, depending on the application type.
Part 5 Field Settings and Test Operation
Field Setting from Outdoor Unit
278