Installation

5 Installation

5.1 Installation Requirements

Installation Environment Requirements
1. Do not install the equipment in a place near flammable, explosive, or corrosive materials.
2. Install the equipment on a surface that is solid enough to bear the inverter weight.
3. The place to install the equipment shall be well-ventilated for heat dissipation and large
enough for operations.
4. The equipment with a high ingress protection rating can be installed indoors or outdoors.
The temperature and humidity at the installation site should be within the appropriate range.
5. Install the equipment in a sheltered place to avoid direct sunlight, rain, and snow. Build a
sunshade if it is needed.
6. Do not install the equipment in a place that is easy to touch, especially within children's
reach. High temperature exists when the equipment is working. Do not touch the surface to
avoid burning.
7. Install the equipment at a height that is convenient for operation and maintenance, and
ensure that the equipment indicator lights, all labels are easy to view, and the wiring
terminals are easy to operate.
8. The altitude to install the equipment shall be lower than the maximum working altitude
4000m.
9. Install the equipment away from electromagnetic interference. If there is any radio or
wireless communication equipment below 30MHz near the equipment, you have to:
• Add a multi-turn winding ferrite core at the DC input line or AC output line of the inverter,
or add a low-pass EMI filter.
• Install the inverter at least 30m far away from the wireless equipment.