Goodwe Smart DT Series User Manual

Goodwe Smart DT Series User Manual

Smart dt series
Hide thumbs Also See for Smart DT Series:

Advertisement

 
 
 
 
 
 
 
 
User Manual 
Smart DT Series 
Ver 02 
 
 
 

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Smart DT Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Goodwe Smart DT Series

  • Page 1           User Manual    Smart DT Series    Ver 02         ...
  • Page 2: Table Of Contents

    Contents   1. Symbols  ..................  1   2. Safety ..................  2   3. Installation .................  5   3.1  Mounting Instruction  ..............  5   3.2  Unpacking .................  6   3.3  Equipment Installation  ..............  8   3.3.1  Selecting the installation position  ........  8   3.3.2  Mounting Procedure ............  1 0  3.4  Electrical Connection  .............  1 3  3.4.1 ...
  • Page 3 4.6  Settings Description  ...............  6 0  4.6.1  Error History Display ...........  6 0  4.6.2  Time Setting  ..............  6 1  4.6.3  Language Setting  ............  6 2  4.6.4  Set the Histogram Display in ‘Year Mode’  ....  6 3  4.6.5  Set Communication Method  ........  6 4  4.6.6  RESET Zigbee ID ............  6 5  4.6.7  Reset WIFI ..............  6 6  4.6.8 ...
  • Page 4: Symbols

    1. Symbols  Caution! ‐ Failure to observe a warning indicated in this     manual may result in minor or moderate injury.  Danger of high voltage and electric shock!    Danger of hot surface!    Product should not be disposed as normal household waste.    This side up ‐ The package must always be transported, handled an stored in such a way that the arrows always point upwards.    Components of the product can be recycled.    Fragile‐The  package/product  should  be  handled  carefully  and  neve be tipped over or slung.    Stack Limitation ‐ 6 units of identical packages that may be stacked  maximum.    Keep  Dry  –  The  package/product  must  be  protected  from  excessive humidity and must accordingly be stored under cover.    CE Mark ...
  • Page 5: Safety

    Figure 2 ‐1  DT  series  inverter  of  Jiangsu  GoodWe  Power  Supply  Technology  Co.,Ltd.  (  hereinafter  referred  to  as  GoodWe  )  strictly  conforms  to  related  safety  rules  in  design  and  test.  As  electric  and  electronic  equipment,  Safety  Regulation  shall  be  followed  during  installation  and  maintenance. ...
  • Page 6 Children must be kept away from inverters.  Please do not open the front cover of inverter. Apart from wiring terminal,  touching  or  changing  components  without  authorization  may  cause  damage  to  people  and  inverters.  GoodWe  may  deny  the  obligation  of  warranty service accordingly.  Static  electricity  may  damage  electronic  components  and  proper  measures shall be adopted to avoid static electricity.   The  output  voltage  of  proposed  PV  array  should  be  lower  than  the ...
  • Page 7 Completely isolate the equipment should :switch off the DC switch ,  disconnect the DC terminal ,and disconnect the AC terminal or AC breaker.  Prohibit inserting or pulling the AC and DC terminals when the inverter is  working.
  • Page 8: Installation

    3. Installation  3.1 Mounting Instruction  A  In order to achieve optimal performance, the ambient temperature should  be lower than 45 °C.  B  For the convenience of checking the LCD display and possible maintenance  activities, please install the inverter at eye level.   C  Inverters  should  NOT  be  installed  near  inflammable  and  explosive  items.  Any electro‐magnetic equipment should be kept away from installation site.  D  Product label and warning symbol shall be clear to read after installation.  E  Please avoiding direct sunlight, rain Exposure, snow lay up when installing, this is better for extended inverter lifetime.      3.1‐1  Figure...
  • Page 9: Unpacking

      3.2 Unpacking  When  you  receive  GoodWe  inverter,  please  check  if  there  is  any  visible  external damage on the inverter or any accessories. Please also check if there  is anything missing according to the list below.  Inverter………………………………………………………………………………………………..………  1  AC junction box…………………........…………………………………………1  AC  terminal  ………………………….………………………………………………………………………6  Positive  DC  Plug…….  …………………...  ...  ……………………….  ...  ..…....……...2  Negative  DC  Plug………………………………………………………………………………..……..…2  USB  Data  Cable……………………………………………………………………...……………...……1  Expansion  Bolt…………………………………………………………………….…………………...…6  Flat  Head  Screw……………………………………………………………………………..…………5 ...
  • Page 10     Wall‐mounted Bracket  AC junction box  Positive DC Plug  Negative DC Plug    AC Terminal  USB Data Cable  Flat Head Screw  Expansion Bolt                   Warranty Card  User Manual PV Inverter        Lock Plate    Pan Head Screw  Antenna    (Only for WIFI Mode)
  • Page 11: Equipment Installation

      3.3 Equipment Installation  3.3.1 Selecting the installation position  Installation position should be selected based on the following aspects:  The  installation  method  and  mounting  location  must  be  suitable  for  the  inverter's weight and dimensions.  Mount on a solid surface.  Select a well ventilated place sheltered from direct sun radiation.  Install vertically or tilted backward by max 15°. The device cannot be              installed with a sideways tilt. The connection area must point downwards.          Figure 3.3.1‐1  In  consideration  of  heat  dissipation  and  convenient  dismantlement,  the  minimum  clearances  around  the  inverter  should  be  no  less  than  the ...
  • Page 12 following value:   Upward    .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .    300mm  Downward    .  .  .  .  ..  .  .  .  .  .  .  .  .  .  .  .  .  .  500mm  Front ...
  • Page 13: Mounting Procedure

    3.3.2 Mounting Procedure     A  Use  the  wall‐mounted  bracket  as  a  template  and  drill  6  holes  on  the           wall, 10 mm in diameter and 80 mm deep.     Figure 3.3.2‐1   B  Fix  the  wall  mounting  bracket  on  the  wall  with  six  expansion  bolts  in  accessory bag.     C   ...
  • Page 14 D      Place the inverter on the wall‐mounted bracket (as illustrated below).     Figure 3.3.2‐3     Figure 3.3.2‐4 E      Fix the inverter with the lock plate in accessory bag (as illustrated below)
  • Page 15                         Figure 3.3.2‐5  F    Use M3*0.5 screw in accessory bag and a padlock to fix the lock plate    on the wall‐mounted bracket (as illustrated below)                                       Figure 3.3.2‐6   ...
  • Page 16: Electrical Connection

    3.4 Electrical Connection  You must comply with the connection requirement of local regulations.  The  inverter  is  integrate  with  an  RCMU  according  to  VDE0126‐1‐1/A1.  It  monitors residual current from the solar module to grid side of inverter.  The  inverter  can  automatically  differentiate  between  fault  current  and  normal  capacitive leakage currents.  It must be included a breaker or a fuse at the AC side, ac breaker’s  norminal voltage is 400Vac, the melting current is not larger than  16A.  The  equipment  should  have  a  protective  earthing  attached  to  earth  conductor.    3.4.1 Connection to Grid (AC Side Connection) ...
  • Page 17   Figure 3.4.1‐1  Open the output cable connection box and loose the remove the screw cap  of the cable gland. Insert the cable through the screw cap and cable gland  as below figure.        Figure 3.4.1‐2 Connect the AC wire as below figure shows: ...
  • Page 18     Figure 3.4.1‐3 Tighten the cables with a torque of 20kgf.cm (1.9 N.m).  Reconnect the AC junction box to the PV inverter  E    Specifications of the AC wires:    Figure 3.4.1‐4  Description  Size  A   External diameter of the wire  11‐20mm  B   Sectional area of conducting materials  4~8mm   C   Length of bare wire  Approx.12mm ...
  • Page 19: Dc Side Connection

    Remarks: Specifications of AC cables should be type of H05VV‐F or similar.  3.4.2 DC Side Connection  A     Make  sure  the  maximum  open  circuit  voltage  (Voc)  of  each  PV  string    does not exceed the inverter input voltage Vmax under any condition.  B       Use   Phoenix or Multi‐contact connectors for PV array terminals. C    Connect  the  positive  and  negative  terminals  of  the  PV  panel  to  corresponding  terminals  on  the  Inverter.  The  DC  terminal  on  each  Inverter  can bear 20A DC current. ...
  • Page 20              Press down on the spring and snap in.            Tighten the screw connection. Then the terminal can be     connected to the inverter side.        The connection can only be released using a screwdriver ...
  • Page 21           Multi‐Contact connector       If  using  Multi‐contact  connectors  for  the  PV  array  terminals,  install  as  follows:                      Female side connector (PV+)     Male side connector (PV‐) Connectors must be installed as a pair, and each cable stripped and installed  as shown below.                  ...
  • Page 22                                              ...
  • Page 23 Tighten  the  screw  connection. Then  the  terminal  can  be  connected to  the  inverter side.           Compress the two snap‐in springs by hand and release.  D     Specifications of the DC wires  The  cable  are  used  outdoor  that  must  comply  with  PV  cable  standards,  as  TUV  2Pfg1169,  Type  PV1‐F,  600V,  90℃  wet.  The  wire  diameters  should  be  2.5‐6 mm .  ...
  • Page 24: Rs485 Communication

    damage the unit.  Checks short‐circuit current of the PV string. The total short‐circuit current  of the PV string cannot exceed the inverter’s maximum DC current.  High voltage exists when the PV panel is exposed to the sun. Please secure  the  terminal  connection,  and  do  NOT  touch  any  exposed  components  in  case of electric shock.   If  you  choose  the  models  without  DC  switch  an  external  disconnection  device  should  be  used.  It  should  be  multi‐pole      switch‐disconnector  (all  poles  disconnected  simultaneously),  which  has  been  approved  according  to ...
  • Page 25 which  communicate  through  one  cable  should  use  provided  RS485  interface  (a  piece  of  10#  cable  is  recommend  to  be  connected  for  waterproofing  without  RS485  cable  connection).  The  typical  inverter  connection graph through RS485 is shown below.    Figure 3.4.3‐1  The  graph  below  shows  the  monitoring  system  connection,  in  which  inverters’ ...
  • Page 26   Figure 3.4.3‐2  Pins of RS485 of GoodWe DT series:    A      Connection procedure: a.  Remove the waterproofRS485 cover;   b.  Remove the screw cap of the cable gland;   c.  Remove the one‐hole sealing ring;  d.  Put the RS485 cable through the components in this order: screw ...
  • Page 27 cap, one‐hole sealing ring, gland body;  e.  Compress the crystal head and insert it into the corresponding  interface;  f.  Replace the waterproofRS485 cover;  g.  Fasten the screw cap of the cable gland.    Figure 3.4.3‐3    B  The RS485 cable has eight wires of different colors. Strip off the outside  envelope to expose the eight wires, then straighten the end of each wire,  and put them in order.    Figure 3.4.3‐4  C  Ensure  each  pin  of  the  crystal  connection  corresponds  with  the  correct  wire of the RS485 cable.  D  Plug  the  eight  wires  into  their  corresponding  slots  of  the  crystal ...
  • Page 28: Zigbee  Communication

    connector, and then fasten them using a 485 wire crimper.  E  Connect  the  other  end  of  the  RS485  cable  to  the  crystal  connector    according to procedures B, C and D. F  The inverter can communicate with an EzLogger through an RS485 cable.  When  the  EzLogger  is  connected  to  a  PC  via  Ethernet  or  USB  interface,  the inverter can communicate with the PC directly.    3.4.4 ZigBee  Communication.  Only for the inverter with ZigBee function(Monitored by EzBee device).  The  ZigBee  communication  function  is  not  compatible  with  the  RS485  communication function. ...
  • Page 29: Wifi Communication

      Figure 3.4.4‐2  3.4.5 WIFI Communication  You  can  browse  GoodWe  global  PV  stations  monitoring  website  (http://www.goodwe‐power.com)  to  get  data.  The  information  includes  energy  generated  yearly,  monthly  and  daily,  the  total  income  and  CO2  savings,  etc.  At  the  same  time  you  can  browse  information  of  other  PV ...
  • Page 30 PV station in advance.   A WIFI router device is essential for Internet connection. Be sure to keep the  inverter in the area that WIFI signal could reach.     ONLY for the inverter with WIFI function:  Step1: Assemble the Antenna.    Figure 3.4.5‐1    As the picture showed, assemble the antenna into the wireless plate.    Step2: Configure Inverter with WIFI  Please start up inverter before the configuration. And make sure the yellow  Led light on the front cover is flickering. Otherwise please set the method to  web referring to 4.6.5 at page 59.    Option I: Via App (for smart phone/pad) ...
  • Page 31 Please download ‘SolarMan Tool’ from google play or app store and install it  on smart phone or Pad. Run it.  Below is for Anroid app:               A. Click ‘Settings’   B. Choose ‘GoodWe‐HF’ ...
  • Page 32             C. Press Configure Icon               D. Choose Enter Manually               E. Input ‘GoodWe‐HF’,              F. Press Next  (no password as default) ...
  • Page 33              G. Choose WiFi network              H. Linking…  And Input password.                                                                                                           I. Repeat A & B, then Press         J. Waiting Diagnose for Result.     ‘Diagnose’ ...
  • Page 34   K. OK or it will tell where there is problem    For iOS app as below:           A. Click ‘Setting’                                     B. Turn on Wi‐Fi...
  • Page 35           C. Choose ‘GoodWe‐HF’                        D. Run app and click Configure           E. Don’t care the ‘Notice’                      F. Press ‘Refresh’ Icon...
  • Page 36          G. Choose Wi‐Fi router network        H. Input password          I. Linking                                        J. Repeat A to C before click to diagnose...
  • Page 37        K. Click ‘I Know’ and Waiting      L. Diagnosing…         M. OK or it will tell where there is problem.  Option II: Via Laptop  You need a PC with WIFI to search WIFI network and choose “GoodWe‐HF”. ...
  • Page 38 Browse website http://10.10.100.254 to set the configuration (user name and  password is the same as “admin”).   In order to avoid the configuration of WIFI module is modified by others, it’s  recommended that you modify the password of WIFI firstly. To implement it  please make ‘AP Interface Setting’. You can find it in the left side of webpage  as below.     Figure 3.4.5‐2    Click  it  and  you  will  get  a  page  and  please  make  the  settings  which  are  marked as below: ...
  • Page 39   Figure 3.4.5‐3    The word “sample” is just a sample, Please change it to your own password.  Please don’t change other settings.  NOTICE: Please do remember the password. Once you forget it and you want  to access it, the only way is to reload the WIFI module. Please refer to 4.7.  Click the “Apply” button, you will get a page as below: ...
  • Page 40   Figure 3.4.5‐4  Then click “STA Interface Setting” and you will get a page as below:    Figure 3.4.5‐5  Left click “Search…” button, you will get a list of WIFI network and choose the  network  of  your  WIFI  router.  “Security  Mode”  and  “Encryption  Type”  will ...
  • Page 41 change the same as your router automaticly. Enter the password of your WIFI  network in “Pass Phrase” column. Do not change the “MAC Address”, “WAN  Connection  Type”  and  “Hostname”,  then  click  “Apply”  button  as  shown  in  picture. You will get a page as below:    Figure 3.4.5‐6  Click the “Device Management”; you will get a page as below:     Figure 3.4.5‐7    Click  the  “Restart”  button,  and  several  seconds  later  the  configuration  is ...
  • Page 42   Step3: Registration   Disconnect the WIFI between your PC and inverter, reconnect to local router.  Browse  http://www.goodwe‐power.com,  and  click  the  “Register”  button.  Select “End User” as user type, fill in the register table and the registration is  completed.    Step4: Create PV Station  Fill  in  the  table  of  the  “New  Station”  web  page  according  to  the  actual  location  of  your  station.  In  the  “Maintain  WIFI  Inverter”  column,  enter  the ...
  • Page 43: Communication With Solar-Log Device

    Code,  Type  and  Description  and  click  “Add”  button.  If  you  got  several  non‐ WIFI type inverters for single PV station, you need to type the information of  inverter one by one.     NOTICE:  ONLY  THE  DATA  FROM  INVERTER  WITH  THOSE  INFORMATION  ENTERED CORRECTLY IN THE WEBSITE CAN BE VIEWED.    3.4.6 Communication with Solar‐Log Device  All GoodWe inverters can be monitored by Solar‐Log200/500/1000.  Work steps     Switch off the inverters and Solar‐Log;     Follow the steps in 3.4.3 connection procedure to install the RS485  interface in the inverters;    Connect inverters to the Solar‐Log;    Connect the inverters to each other;   CAUTION!  Risk of damage to the Solar‐Log!  The Solar‐Log also has an RJ45 socket, which must never be connected to the ...
  • Page 44 RJ45 socket on the inverter!    ONLY  connect  Solar‐Log  via  the  RS485/422  B  interface  on  the  bottom  of  Solar‐Log.    Figure 3.4.6‐1 RS485/422 B Terminal Block Connector  Connect the wires as shown in the following diagram:  Solar‐Log terminal block connector RJ 45 socket of inverter Pin 1  Pin 6  4  Pin 3  5  Pin 8  6  Pin 7    Insert the RJ45 plug into any RJ45 socket on the first inverter;    If only one inverter is to be connected, terminate this;    Insert  the  terminal  block  connector  into  the  Solar‐Log  RS485/422  B  socket; ...
  • Page 45: Usb Communication

    Connecting the inverters to each other  Connect using a network cable (patch cable);  Where to connect: RJ45 socket on the outside of the inverter;  Procedure:    Insert the RJ45 plug into any RJ45 socket on the first inverter;    Insert the other end of the wire into any RJ45 socket on inverter 2;    Connect the other inverters to each other in the same way;    Terminate in the last inverter;  Notice: Before operation, please read the instruction of Solar‐Log!    3.4.7 USB Communication.  USB communication function is available for all GoodWe inverters. Before use  the  function  please  installs  software  ‘EzExplorer’  which  can  be  downloaded  from GoodWe website.  USB data cable can be connected as below.  A  Take off the USB socket cover.  B  Insert USB cable as the arrow pointed out.           ...
  • Page 46: Troubleshooting

      Figure 3.4.7‐1    3.5 Troubleshooting  If  the  Inverter  is  not  able  to  work  properly,  please  refer  to  the  following  instructions before contact your local service.  Should  any  problems  arise,  the  red  (FAULT)  LED  indicator  on  the  front  panel  lights  up  and  the  LCD  screen  will  display  relevant  information.  Please ...
  • Page 47   1. The ground current is too high.  2. Unplug the inputs from the PV generator and check the  Ground I Failure  peripheral AC system.  3. When the problem is cleared, reconnect the PV panel and check  the Inverter status.  4. Contact local service office for help if the problem still exists.    1. The PV Inverter will automatically restart within 5 minutes if the  grid returns to normal.  Vac Failure  2. Make sure grid voltage is in conformity with the specification.  3. Contact local service office for help if the problem still exists.    1. The PV Inverter will automatically restart within 5 minutes if the  grid returns to normal.  Fac Failure  2. Make sure grid frequency is in conformity with the specification. 3. Contact local service office for help if the problem still exists.  1. Grid is not connected.  Utility Loss  2. Check grid connection cables.  3. Check grid usability.    1. Check whether the PV open voltage is higher or too close to the  maximum input voltage.  Inverter  PV Over Voltage  Failure  2. If the problem still exists when PV voltage is less than the  maximum input voltage, contact local service office for help.   ...
  • Page 48   1. Disconnect PV (+) or PV (‐) from the input and restart the PV  Inverter.  Consistent Failure 2. If the problem still exists, contact local service office for help.      1. The internal temperature is higher than normal value specified. 2. Reduce ambient temperature.  Over Temperature 3. Move the inverter to a cool place.  4. If the problem still exists, contact local service office for help.    1. Disconnect all PV (+), PV (‐) and Grid.  2. Refer to Chapter 7 ‘Maintenance’ to clean the external fans.   Ext Fan Failure  3. Reassembly the fans and check again.  4. If the message appears again, contact local service office for  help.  Int Fan Failure  Please contact local service office for help.  All Fans Failure  Relay‐Check  Failure  1. Disconnect all PV (+) or PV (‐).  DC Injection High 2. Wait for a few seconds.  EEPROM R/W  3. After the LCD switches off, reconnect and check again.  Failure  4. If the message appears again, contact local service office for  help.  SCI Failure  DC Bus High ...
  • Page 49 Ref 2.5V Failure  GFCI Failure  WiFi  1.Check the yellow led light on front cover is flickering or not; If  not, set protocol to Web. Refer to 4.2.2;    Failure 2. Make sure the configuration was made step by step follow the  guide. Otherwise, please configure the WiFi properly.  3. If you forget the password you set for WiFi module in inverter,    and you want to access the WiFi module once again, you can use  the button to reload WiFi module. Please refer to 4.6.8  4. Check if the WiFi router can access to internet or not.  5. Make sure the inverter is not far away from the WiFi router than  10 meters. If yes, please locate the WiFi router closer to inverter. If  there  is  no  display  on  the  panel,  please  check  PV‐input  connections.  If  the voltage is higher than 250V, contact local service office for help.       When  sunlight  is  insufficient,  the  PV  Inverter  may  continuously  start  up  and shut down automatically due to insufficient power generated by the ...
  • Page 50: System Operation

    4. System Operation  4.1 Functions of Indicating Lights           Yellow light:  For Non‐WIFI type  Light on indicates the inverter is electrified;   Light off indicates the inverter is not electrified.     For WIFI type Light flashes on 1sec off 1sec indicates the WIFI module doesn’t connect  to the WIFI network; Light flashed on 2.5sec off 2.5sec indicates the WIFI  module  connect  to  the  WIFI  network  but  cannot  receive  data  from  Web  Server; Always on indicates communication between Web Server is OK.    Green light:   If  on,  inverter  is  generating  electricity;  if  off,  inverter  is  not  generating  electricity. if flashing, inverter is self‐checking. ...
  • Page 51: Lcd Display Descriptions

    Red light:   If on, abnormal conditions appear; if off, no abnormal conditions appear.  There are 4 keys in total: UP, DOWN, ESC, ENTER. Press one of them can  alter the content to be displayed. The operation instruction of key will be  described below in details.    LCD Display Descriptions  The Figure of LCD display screen is shown as follow:     Illustration of the specific area of the display screen:   The display area is divided to four sectors: top, middle‐left, middle‐right,  bottom. ...
  • Page 52: Top Area - Flow Of Power Generated

    About  the  settings  of  field  adjustable  setpoints  shall  be  accessible  from  communications port.  4.2.1 Top Area – Flow of Power Generated  This area indicates the flow of energy. Flashing dash lines between the sun,  modules and inverter means there is energy from the sun to modules and  then  from  modules  to  inverter.  Full  line  between  inverter  and  the  grid  means  the  grid  is  available  but  inverter  is  not  yet  feeding  power  at  the  time. Flashing dashing lines mean inverter is feeding power to grid. No line ...
  • Page 53   Figure 4.2.2‐1 First level menu ...
  • Page 54                       Second level menu (WIFI Model)           Second level menu (Non‐WIFI Model)  Figure 4.2.2‐2 ...
  • Page 55 Items  of  the  level  2  and  level  3  regarding  the  ‘Error  Log’  are  listed  and  shown  in  the  Figure  4.2.2‐3.    Right  side  of  Figure  4.2.2‐2  indicates  the    items of level 3.     Figure 4.2.2‐3    Items of the level 2 and level 3, regarding the ‘Date & Time’, are listed and  shown  in  the  Figure  4.2.2‐3.  Press  ‘ENTER’  for  2  seconds  to  save  the ...
  • Page 56 setting or press ‘ESC’ to discard the setting.         Figure 4.2.2‐4 Items of the level 2 and level 3, regarding ‘Language’, are listed and shown  in  the  Figure  4.2.2‐5.  Press  ‘ENTER’  for  2  seconds  to  save  the  setting  or  press ‘ESC’ to discard the setting.  ...
  • Page 57      Figure 4.2.2‐5 Items  of  the  level  2,  level  3  and  level  4,  regarding  ‘Histogram’,  are  listed  and shown in the Figure 4.2.2‐6.   Error Log Year Mode Year Mode Date&Time Month Mode Enter Enter Language Day Mode Histogram Hour Mode 2012 Down Year Mode Month Mode Month Mode Down Month Mode...
  • Page 58     Figure 4.2.2‐7 Items of the level 2, level 3, regarding ‘WIFI Reset’, are listed below in the  Figure 4.2.2‐8       Figure 4.2.2‐8 Items of the level 2, level 3, regarding ‘WIFI Reload’, are listed and shown  in the Figure 4.2.2‐9      Figure 4.2.2‐9...
  • Page 59: Right Middle Area-Histogram Display

    Items of the level 2, level 3, regarding for set 70% rated load, are listed and  shown in the Figure 4.2.2‐10      Figure 4.2.2‐10 Items of the level 2, level 3, regarding for set 70% rated load, are listed and  shown in the Figure 4.2.2‐9      Figure 4.2.2‐11 4.2.3 Right Middle Area—Histogram Display  This area use histogram to demonstrate the average power generation at  each  hour  from 4:00am  to  8:00pm  on  one  day.  Each  columnar points  20  scale,the left top area shows the maximum rated power generation each  hour for inverter.   This  area  can  display  information  in  different  modes,  such  as  power  generation  in  recent  10  years;  daily  power  generation  of  recent  year, ...
  • Page 60 which can be realized through key operation. There are 5 display mode in  total: real‐time mode, hour mode, day mode, month mode, year mode.  Real‐time  mode:  display  hourly  power  generation  from  4:00am  the  current day;  Hour  mode:  display  the  hourly  power  generation  in  a  specific  day  from  recent 31 days;  Day  mode:  display  the  daily  power  generation  in  a  specific  month  from  recent 12 months;  Month  mode:  display  the  monthly  power  generation  for  12  months  in  specific year; ...
  • Page 61: Bottom Area

    4.2.4 Bottom Area  Displays  total  power  generation,  daily  power  generation,  and  power    generated at present and time information, described as follow:  Area  Description  E‐DAY  Power generated the current day  Gross power generated from the first time use of inverter.  E‐TOTAL  The initial unit is “KWh”; When power generation exceeds  999.9kWh, the unit changes to “MWh”.  TIME  Current system time  POWER  Instant power generation of the system    Table 4.2.4‐1 Key Operation and LCD Description  4.3.1 Key Description  There are 4 keys in total: UP, DOWN, ESC, ENTER.  UP,  DOWN:  move  up/down  at  current  menu  or  adjust  figures  in  setting  menu. ...
  • Page 62: Key Operation And Lcd Description

    4.3.2 Key Operation and LCD Description   Key operation is mainly for LCD display of the switching information such  as settings of time, language and histogram information display.  The  menu  in  LCD  display  area  has  three  levels;  In  the  first‐level  menu,  pressing  ‘ENTER’  in  the  last  menu  can  enter  second‐level  menu.  For  the  rest, press ‘ENTER’ to lock current interface, the backlight will be on for 3  minutes and turned off automatically afterwards;Press any key to unlock  the interface for information display, the backlight will be kept on for 20S  and then enter the default initial interface.   In  second‐level  menu,move  the  cursor  to  the  setting  area  through  ‘DOWN’ ...
  • Page 63: Start Up Introduction

    Press  any  key  once  to  turn  on  the  LCD  backlight  when  it  is  off;  if  the  backlight is on, press ‘DOWN’ key to enter the next menu displaying data  of Vpv and Ipv; press ‘ENTER’ to lock the current interface.  In the first level menu, the displayed information can be switched through  ‘DOWN’ and ‘UP’ key operation, there are 7 interfaces in total, which are  circulatory.  The  second‐level  menu  can  only  be  selected  through  ‘ENTER’  from  the  seventh interface.  In the second‐level menu, third‐level menu can only be accessed through  ‘Histogram’.  Start up Introduction  When  the  input  voltage  reaches  inverter  turn‐on  voltage,  LCD  starts  to  work ...
  • Page 64: Time Setting

    Step 1: press ‘UP’ or ‘DOWN’ key once to turn on the backlight; and then  press ‘UP’ once,or ‘DOWN’ 6 times to enter the seventh interface of the  first‐level menu, press ‘ENTER’ enter the second‐level menu, it displays as  following:    Step  2:  ’Error  Log’  flicking,  which  indicates  the  cursor  current  position,  press ‘ENTER’ to enter the interface shown below:    This  interface  shows  the  latest  error  message  and  time;  press  ‘DOWN’  key  .  switching to the next error message 4.6.2 Time Setting  Step  1:  Enter  the  second‐level  menu,  then  press  ‘DOWN’  key  to  enter  following interface:  ...
  • Page 65: Language Setting

      Step 3: Press ‘UP’ or ‘DOWN’ key to set the ‘hours’. Press ‘ENTER’ to move  the  cursor  to  the  minutes  setting  area  as  following  interface  if  needed.     The  years/months/days  setting  can  be  done  in  the  same  manner,  when  the setting is completed, press ‘ENTER’ for 2sec to store setting value and  enter  previous  menu  or  press  ‘ESC’  to  discard  setting  value  and  enter  previous  menu,  press  ‘ESC’  again  to  enter  first‐level  menu;  The  interface  can also automatically enter first‐level menu if key operation for 20S.  ...
  • Page 66: Set The Histogram Display In 'Year Mode

      Step 3: Press ‘DOWN’ or ‘UP’ to select the language(As far as now, ONLY  English  is  available),  press  ‘ENTER’  or  ‘ESC’  to  enter  previous  menu,  press  ‘ESC’  again  to  enter  first‐level  menu;  if  no  key  operation for 20S, the interface will automatically enter first‐level  menu.   4.6.4 Set the Histogram Display in ‘Year Mode’  Step  1:  Enter  the  second‐level  menu,  then  press  ‘DOWN’  key  thrice  to  enter following interface:   Error Log Data&Time Language...
  • Page 67: Set Communication Method

        4.6.5 Set Communication Method  Caution!  This  function  is  only  used  for  the  service  person.  Misuse  will  cause  the  communication failed.  Enter  the  second‐level  menu,  then  press  ‘DOWN’  key  4  times  to  enter  the  following interface:    ‘Set Local’ means inverter works under WIFI mode.  Long press ‘Enter’ it will change the communication method from WIFI mode  to Local mode, see the below:  Set Web Zigbee ID  ...
  • Page 68: Reset Zigbee

    Long press ‘Enter’ it will change the communication method from Local mode  to WIFI mode.  4.6.6 RESET Zigbee ID  Only  for  the  Zigbee  function  inverter  (with  EzBee  device).  When  the  communication  between  inverter  and  EzBee  is  failed,  please  try  to  reset    ZigBee ID.   Enter second level manual, then press ‘DOWN’ key to select ‘Zigbee ID’ in the  below interface:  Set Web Zigbee ID   Short press ‘Enter’ to enter below interface:    Long press ‘Enter’ to start Zigbee ID reset: ...
  • Page 69: Reset Wifi

      After several seconds the screen will show the set is successful or failed:   or    Press ‘ESC’ to quit.  4.6.7 Reset WIFI  Only  For  WIFI  function  inverter.  When  the  WiFi  communication  is  failed,    please try to please try to use the function. Enter  second  level  manual,  then  press  ‘DOWN’  key  to  select  ‘WIFI  Reset’  in  the blow interface:  Set Local WiFi Reset WiFi Reload  ...
  • Page 70: Reload Wifi

      Long press ‘Enter’ to start WIFI reset:    After several seconds the screen will show the set is successful or failed.   or    Press ‘ESC’ to quit.  4.6.8 Reload WIFI  Only  For  WIFI  function  inverter.  WiFi  reload  function  is  used  to  change  the  WiFi configuration to default value. Please configure the WiFi again as 3.4.5    after using the function. Enter second level manual, then press ‘DOWN’ key to select ‘WIFI Reload’ in  the blow interface: ...
  • Page 71: Set 70% Rated Load

    Set Local WiFi Reset WiFi Reload   Then the same operations as ‘WIFI Reset’.  4.6.9 Set 70% Rated Load  CAUTION!  The  function  is  only  for  using  with  VDE  AR‐N  4105  standard  and  only  for  service  person.  Misuse  will  cause  the  inverter  derating.  This  menu  is  not  shown for other standards.  Enter  second  level  manual,  then  press  ‘DOWN’  key  to  select  ‘WIFI  Reset’  in  the blow interface: ...
  • Page 72: Error Message

    Long press ‘Enter’ the output power will be limited to 70%.  The  interface  shows  ‘100%  rated’  means  the  inverter  is  70%  output  power.  Long press ‘Enter’ the output power will recover to 100%.  Error Message  An  error  message  will  be  displayed  on  LCD  interface  when  a  disturbance    occurs. The error message and its description are shown in table below:   Error Message  Description  Utility Loss  Grid disconnection/fault  Fac Failure  Grid frequency out of range  Consistent Failure  Machine parameter consistent fault   Int Fan Failure  Internal Fan Failure  Ext Fan Failure  External Fan Failure ...
  • Page 73 DC Bus High  Overhigh BUS voltage  AC HCT Failure  Output current sensor failure  GFCI Failure  Detection circuit of ground leakage current failure  Vac  Failure  Grid voltage no longer within permissible range  Ref 1.5V Failure  1.5V reference voltage failure  Table 4.7‐1...
  • Page 74: Technical Parameters

    5. Technical Parameters            5.1  Technical Parameters   Model Name  GW4000‐DT  GW5000‐DT  GW6000‐DT  DC input Data  Max. PV‐generator power [W]  4200  5200  6200  Max. DC Voltage [V]  1000  MPPT voltage range [V]  200~800  Turn on DC Voltage [V]  180  Max. DC work current [A]  11/11  Isc PV [A]  16/16  Max Inverter backfeed current to the  0  array[A]  Number of MPP trackers  2(can parrallel)  DC‐connection  MC  IV Connector(Optional)  Turn on power [W]  10  AC Output Data  Norminal AC power[W]  4000  5000  6000  Max.AC power[W]  4000  5000  6000 ...
  • Page 75 Euro efficiency  >96.7%  MPPT adaptation efficiency  >99.5%  Safety Equipment  Residual current monitoring unit  Integrated  DC disconnect switch  Option  Islanding protection  AFD  According to VDE‐AR‐N 4105, VDE0126‐1‐1/A1,RD1699,  Grid Monitoring  G83/1,AS4777.2/.3  Normative Reference  EMC‐ compliant according to  EN 61000‐6‐1,EN 61000‐6‐2,EN 61000‐6‐3,EN 61000‐6‐4  Safety compliance  According to  IEC62109‐1/2, AS3100  General Data  Dimensions (WxHxD) [mm]  516*192*474  Net Weight [kg]  24  Environmental category   outdoor and indoor  Mounting information  Wall bracket  Ambient temperature range  ‐20~60°C(up 45°C derating)  Relative humidity  0~95%  Wet locations classification 4K4H  UV exposure rating  F1  Ⅲ  AC Overvoltage category  Ⅱ  DC Overvoltage category  Site altitude[m] ...
  • Page 76 Model Name  GW4000L‐DT  GW5000L‐DT  GW6000L‐DT  DC input Data  Max. PV‐generator power [W]  4200  5200  6200  Max. DC Voltage [V]  600  MPPT voltage range [V]  200~500  Turn on DC Voltage [V]  180  Max. DC work current [A]  11/11  Isc PV [A]  16/16  Max Inverter backfeed current to  0  the array[A]  Number of MPP trackers  2(can parrallel)  DC‐connection  MC  IV Connector(Optional)  Turn on power [W]  10  AC Output Data  Norminal AC power [W]  4000  5000  6000  Max.AC power [W]  4000  5000  6000  Max.output current[A]  7  8.5  10 ...
  • Page 77 Islanding protection  AFD  According to VDE‐AR‐N 4105, VDE0126‐1‐1+A1,  Grid Monitoring  G59/2, AS4777.2/.3, IEC62109‐2  Normative Reference  EMC‐ compliant according to  EN 61000‐6‐1,EN 61000‐6‐2,EN 61000‐6‐3,EN 61000‐6‐4  Safety compliance  According to  IEC62109‐1/2, AS3100  General Data  Dimensions (WxHxD) [mm]  516*192*474  Net Weight [kg]  24  Environmental category   outdoor and indoor  Mounting information  Wall bracket  Ambient temperature range  ‐20~60°C(up 45°C derating)  Relative humidity  0~95%  Wet locations  4K4H  classification  UV exposure rating  F1  Ⅲ  AC Overvoltage category (note2)  Ⅱ  DC Overvoltage category  Site altitude[m]  2000  IP protection type  IP65  Topology  Transformerless  Cooling concept  Nature Convection  Noise level[dB] ...
  • Page 78 is not considered OV category IV.  •  category  III  applies  to  equipment  permanently  connected  in  fixed  installations(downstream of, and including, the main distribution board). Examples are  switchgear and other equipment in an industrial installation;  •  category  II  applies  to  equipment  not  permanently  connected  to  the  fixed  installation.Examples  are  appliances,  portable  tools  and  other  plug‐connected  equipment;  •  category  I  applies  to  equipment  connected  to  a  circuit  where  measures  have  been taken to reduce transient overvoltages to a low level. ...
  • Page 79: Temperature Derating Character

    5.2 Temperature Derating Character   Typical temperature derating curve of GW6000‐DT as follow:   ...
  • Page 80: Certificates

    6. Certificates                                         ...
  • Page 81: Maintenance

    7. Maintenance  Regular maintenance ensures a long operating life and optimal efficiency  of the entire PV plant.    7.1 Checking the DC Switch  DC switch does not require any maintenance. It is recommended that:  • Check the DC switch regularly.  • Activate the DC switch 10 times in a year.  Operating the switch will clean the contacts and will extend the life of the  DC switch.    Warning:  Don’t touching other areas of the inverter!
  • Page 82: Warranty

    According  to  GoodWe  product  description  and  instruction,  if  a  device  becomes  defective  within  warranty  period,  and  it  is  proved  that  further  functional performance is impossible due to product quality problem, the  device will be, as selected by GoodWe:  A    Return to the factory for maintenance;   B    Onsite maintenance;   C    Products Replacement;   If  the  original  model  has  stopped  in  production,  GoodWe  will  provide  a  replacement device of equivalent value according to model and age.     ...
  • Page 83: Scope Of Warranty

    8.4    Scope of Warranty  Warranty declaration is excluded in the following situations:  Products  or  fittings  exceed  warranty  period  (exclude  the  warranty  extension agreement signed beforehand).  Fault  or  damage  due  to  improper  operation  without  following  user  manual, product instruction, and relevant safety regulations.  Insufficient ventilation of the unit .  Fault or damage due to improper installation, repair, change or removal by  persons who are not authorized by GoodWe.  Fault or damage due to unpredictable accidental factors, human errors or  force majeure.  Fault or damage which is not caused due to products quality problem.   ...
  • Page 84: Contact

    9. Contact  If you have any enquiries or technical problems concerning GoodWe DT series  inverter, please contact our customer services.  Add: No.189 Kun Lun Shan Road, Suzhou New District, Jiangsu, China (Jiangsu  GoodWe Power Supply Technology Co., Ltd.)  Tel:  + 86 512 6239 6771  Fax: + 86 512 6239 7972  E‐mail: service@goodwe.com.cn  Website: www.goodwe.com.cn   ...