6.5.2 DRM Mode Description

DRM Function Wiring Diagram
The inverter supports DRMO and DRM5-8 modes. The requirements
for each mode are as follows:
Mode
Inverter
port
DRM0
COM/
DRM0
DRM5
DRM1/5
DRM6
DRM2/6
DRM7
DRM3/7
DRM8
DRM4/8
DRM device
Requirement
Turn on S0 and the inverter shuts down.
Turn off S0 and the inverter is back to on-grid.
Turn on S5 and the inverter does not output
Active Power.
lurn on S6 and the inverter outputs Active Power
no more than 509 of its rated power.
Turn on S7 and the inverter outputs Active Power
no more than 7596 of its rated power. In the
meantime, the inverter consumes the maximum
Reactive Power.
Turn on S8 and the inverter is back to Active
Power output.
31
Electrical Connection
RCR
Description
-
When two or
more than 2
DRMs are working
simultaneously, select
any two of them that
can satisfy the strictest
requirement.