Maintenance
No.
Fault
10min
5
overvoltage
protection
Grid
6
Overfrequency
Cause
The moving average of
grid voltage in 10min
exceeds the range of safety
requirements.
Utility grid exception.
The actual grid frequency
exceeds the requirement of
the local grid standard.
User Manual V1.1-2023-12-30
Solutions
1. If the problem occurs occasionally,
the utility grid may be abnormal
temporarily. The inverter will recover
automatically after detecting that the
utility grid is normal.
2. Check if the power grid voltage has
been operating at a high voltage for
a long time. If it occurs frequently,
please check if the power grid voltage
is within the allowable range.
• Contact the local power company
if the grid voltage exceeds the
permissible range.
• Modify the grid overvoltage
rapid protection threshold after
obtaining the consent of the local
power company if the grid voltage
is within the permissible range.
1. If the problem occurs occasionally,
the utility grid may be abnormal
temporarily. The inverter will recover
automatically after detecting that the
utility grid is normal.
2. If the problem occurs frequently,
check whether the grid frequency is
within the permissible range.
• Contact the local power company
if the grid frequency exceeds the
permissible range.
• Modify the overfrequency
protection threshold or disable the
overfrequency protection function
after obtaining the consent of the
local power company if the grid
frequency is within the permissible
range.