Installation; Installation Requirements - Goodwe ET Series User Manual

Hybrid inverter 5.0-10.0kw ac-coupled inverter 5.0-10.0kw
Hide thumbs Also See for ET Series:
Table of Contents

Advertisement

05 Installation

5 Installation

5.1 Installation Requirements

Installation Environment Requirements
1. Do not install the equipment in a place near flammable, explosive, or corrosive materials.
2. Do not install the equipment in a place that is easy to touch, especially within children's reach.
High temperature exists when the equipment is working. Do not touch the surface to avoid
burning.
3. Avoid the water pipes and cables buried in the wall when drilling holes.
4. Install the equipment in a sheltered place to avoid direct sunlight, rain, and snow. Build a
sunshade if it is needed.
5. The place to install the equipment shall be well-ventilated for heat dissipation and large
enough for operations.
6. The equipment with a high ingress protection rating can be installed indoors or outdoors.
The temperature and humidity at the installation site should be within the appropriate range.
7. Install the equipment at a height that is convenient for operation and maintenance, electrical
connections, and checking indicators and labels.
8. The inverter shall be installed below the maximum operating elevation of 4000m.
9. Install the equipment away from electromagnetic interference. If there is any radio or
wireless communication equipment below 30MHz near the equipment, you have to:
• Add a multi-turn winding ferrite core at the DC input line or AC output line of the inverter,
or add a low-pass EMI filter.
• Install the inverter at least 30m far away from the wireless equipment.
Children No Touch
22
User Manual V1.1-2022-12-20
≥300mm
≥200mm
≥300mm
≥500mm
≥200mm

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents