An AC circuit breaker should be installed on the AC side to make sure that the inverter can safely
disconnect the grid when an exception happens. Select an appropriate AC circuit breaker in
compliance with local laws and regulations. The following switches are for reference:
Inverter Model
GW700-XS-30
GW1000-XS-30
GW1500-XS-30
GW2000-XS-30
GW2500-XS-30
GW3000-XS-30
GW3300-XS-30
GW3300-XS-B30
The inverter needs to be externally connected with an A type RCD (residual current monitoring
device) for protection when the DC component of the leakage current exceeds the limit value.
The following RCDs are for reference:
Inverter Model
GW700-XS-30
GW1000-XS-30
GW1500-XS-30
GW2000-XS-30
GW2500-XS-30
GW3000-XS-30
GW3300-XS-30
GW3300-XS-B30
• When wiring, the AC output cables and the "L", "N", and "PE" ports of the AC terminal need
to be perfectly matched. If the cable connection is incorrect, it will cause damage to the
inverter.
• Ensure that the whole cable cores are inserted into the AC terminal holes. No part of the
cable core can be exposed.
• Ensure that the cables are connected securely. Otherwise, the operation of the equipment
may cause overheating of the wiring terminals and damage to the inverter.
• Avoid excessive bending of cables.
AC Switch Specification
WARNING
25
Electrical Connection
16A
25A
RCD Specification
300mA