Operation Mode Local - AUMA SG 03.3 Operation Instructions Manual

Electric part-turn actuators
Table of Contents

Advertisement

Part-turn actuators SG 03.3 – SG 04.3
with AUMATIC AC 01.1

16.2 Operation mode LOCAL

16.3 Operation mode REMOTE
16.4 Operation mode EMERGENCY The actuator can be brought to a programmed EMERGENCY position by
EMERGENCY operation behaviour:
52
Fig. P3
Fig. P4
removal of the signal EMERGENCY (see wiring diagram
ACP ... KMS TP ...).
As the signal EMERGENCY works active-low, 24 V must be supplied to
contact X
Pin 1 in the normal state. An emergency operation is performed
K
when the signal is interrupted.
.
An EMERGENCY operation is performed either in selector switch position
LOCAL or REMOTE or only in REMOTE (parameter "
.
", page 32)
MODE
No emergency operation is performed when the selector switch is in
position OFF.
The operation mode EMERGENCY has the highest priority.
(Parameter "
EMERGENCY BEHAVIOUR
Simple EMERGENCY operation behaviour "
An EMERGENCY operation is only triggered when the EMERGENCY signal
at the EMERGENCY input falls from 24 V to 0 V, i.e. only if a 24 V signal
was previously connected to the EMERGENCY input.
Set selector switch (figure P3) on the local con-
trols to position LOCAL.
.
The actuator can be controlled by the push
buttons OPEN - STOP - CLOSE
.
(figure P1).
A change-over between push-tu-run
operation and self-retaining is possible (page
.
55, subclause 16.10).
Faults (refer to pages 25, 26) and warnings
without automatic Reset must be confirmed
with the push button "Reset".
Set selector switch (figure P4) on the local con-
trols to position REMOTE.
.
The actuator is controlled by external
.
REMOTE commands OPEN, STOP, CLOSE.
A change-over between push-to-run
operation and self-retaining (page 55,
subclause 16.10) is possible.
", page 32)
GOOD SIGNAL FIRST
Operation instructions
EMERGENCY
":