The Settings Of Outdoor Unit And System Controller Lite - Fujitsu AIRSTAGE UTY-ALGX Instruction Manual

System controller lite for vrf system
Table of Contents

Advertisement

36.
The Settings of Outdoor Unit and System
Controller Lite
In order to understand the appropriate power consumption with the System Controller Lite, it is important to
correctly transmit the electricity value measured with the power meter.
In order to do this it is necessary to configure appropriate settings on the power meter, outdoor unit, and
System Controller Lite.
The following describes the method of setting the pulse value on the controller.
Setting example
If the electricity meter you are using has units of pulses specified.
Electricity meter
VT
(PT)
VT
Pulse unit setting
(PT)
point
Electricity meter
Pulses output with electricity meters specified in units of pulses are normalized (usually 1kWh/pulse) be-
forehand and then output.
Set location
Setting items
Configuration fol-
Electricity
lowing the product
meter
manual.
Meter number setting Any
Outdoor unit
Electricity meter
pulse setting
Electricity meter sys-
tem settings
System Con-
troller Lite
Pulse setting
[Setting Examples]
Setting conditions: VT ratio = 1 (unused), CT ratio = 50 (250/5A), power meter = 1kWh/ pulse
Set value: Electricity meter pulse setting = 1 (fixed), pulse setting = 1 (for the electricity meter used)
Copyright© 2013-2015 Fujitsu General Limited. All rights reserved.
Pulse transmission line
to CN135
Service line for
measurement use
Outdoor unit
CT
Power cable
Indoor unit
Service line for
measurement use
Transmission line (VRF Network)
Pulse transmission line
Set value
Comment
If the product has fixed settings,
configure by following the prod-
-
uct manual (pulse unit value,
VT/CT ratio, output factor, etc.).
In order to distinguish between
power meters, configure a fixed
power meter number
Set it fixed at "1".
When one pulse comes from
1
the electricity meter, the out-
door unit will communicate "1"
to the System Controller Lite.
Unit that is subject
The electricity meter with the
to measurement
meter number set in the out-
by the electricity
door unit configures the mea-
meter
sured outdoor and indoor units.
The electricity meter is set to
Electricity meter
the specified pulse units without
pulse unit value
them being changed.
(normally it is
Set the number of kWh that
either of 1, 10, or
corresponds to the "1" commu-
100 [kWh/pulse])
nicated from the outdoor unit.
299
System Controller Lite
to CN135
Remarks
These information are
required for System
Controller Lite setting.
Please refer to the
Installation Manual of the
outdoor unit.
Use values set for each
outdoor unit
Refer to values set for
each outdoor unit