Peak Cut Operation Display - Fujitsu AIRSTAGE UTY-ALGX Instruction Manual

System controller lite for vrf system
Table of Contents

Advertisement

555555

Peak cut operation display

To display this screen, Select main screen menu →"Operation" →"Energy Saving".
Outdoor unit stop range
Forced thermostat off range
Warning range
Set temperature
shift range
Ideal control line
(Use of average power consumption)
It displays that peak cut control is "Active" or "Not Active".
The function of peak cut control icon is as follow. (This will be displayed only when the Peak Cut Operation is Active.)
The stand-by state before peak cut control beginning.
The control will begin from the next period.
Standby
The status will become the standby status when the System Controller Lite is started, or
the Peak Cut Period value is changed.
When peak cut control and average electricity reach a warning range of 5% from the
Warning
lower limit line of forced thermostat off range.
When peak cut control and average electricity reach forced thermostat off range and
Thermo Off
forced thermostat OFF control is started.
When the Peak Cut Control/Average Electric Power has reached Forced thermostat off
Forced off
range and Outdoor Unit Stop Control has started.
Target power consumption
Shows change in power consumption by time
Copyright© 2013-2015 Fujitsu General Limited. All rights reserved.
236
(c)
(a)
(b)
(d)
5
.