Fujitsu AIRSTAGE UTY-ALGX Instruction Manual page 96

System controller lite for vrf system
Table of Contents

Advertisement

Note
If the following message is displayed after scanning is completed, the necessary information cannot be
acquired.
"Information was not acquired for some units. Perform unit registration again."
In this case, always perform scan again to acquire all the necessary information.
If advanced to next as is, normal operation will become impossible.
Especially, if there is a unit for which information could not be acquired when electricity charge apportion-
ment is performed, the refrigerant system including that unit will not be handled by the electricity charge
apportionment function.
When these information missing units are included in "Unit Newly Detected", since they are displayed in
red characters, treat them as the index of refrigerant system specification when rescanning.
Unit newly detected list:
After the end of scanning, displays the units newly detected.
At initial scanning, all the units are displayed.
After the 2nd scanning, only the units newly detected are displayed.
Model names for S/V series will not be displayed.
Note
Depending on the R/C connected to the indoor unit, "R/C address" part of the "Address No." column may
show different value from that being set to the indoor unit.
The same applies to the "Address No." and "Address" column of other screens.
The numbers in the "Address No." corresponds to "Refrigerant system address" - "Unit address" - "R/C
address".
5
Unit not detected list:
When scanning was performed for the 2nd and subsequent times, displays the units which are already
registered and were not detected this time.
Note
As a result of performing scan, a unit of the same address may be displayed in the Unit Newly Detect-
ed list and Undetected Unit list.
This occurs when a registered unit was changed to a different model and set to the same address as
the previous unit, etc.
Since the registration information of the previous unit is erased when registration is completed, con-
tinue at that setting.
When intentionally removing a unit from registration, etc, because the unit is removed from the electric
power charge apportionment objective or other reason, confirm it here. (Perform scanning after turning
off the power of the unit removed from registration.)
[OK] button:
Saves the detected unit configuration detected by scanning.
(At initial starting, [Back]: Returns to Transmission adaptor setting)
[Cancel] button:
Ends scanning without saving the scanned result.
(At initial starting, [Next]: Advances to unit name registration)
To perform setting at initial starting, advance to par. 8-3-4 Unit name registration by clicking the
[Next] button.
Copyright© 2013-2015 Fujitsu General Limited. All rights reserved.
96