Fujitsu AIRSTAGE UTY-ALGX Instruction Manual page 292

System controller lite for vrf system
Table of Contents

Advertisement

Installation limitations
Only install air-conditioning units which are to be in-scope for the function.
If an electric lamp or other OA equipment is connected to the electricity meter, also take into account
the amount of power they use.
Make it so that the electricity meter is only connected to required air-conditioning units.
Only connect the meter to V-II/V-III/VR-II/J-II/J-IIS Series air-conditioners.
Electricity meters can only be installed on V-II/V-III/VR-II/J-II/J-IIS Series equipment. Do not connect
the electricity meter to S Series or V Series, as these do not support it.
You cannot have a mixture of units that support the electricity meter and those that do not support it
working under a single electricity meter.
This is because the functions that can be used are different.
If connecting Single split AC using the V-II/V-III/VR-II/J-II/J-IIS series' network converter (UTY-VGGXZ1),
please separate the connection between the V-II/V-III/VR-II/J-II/J-IIS series VRF air conditioner and
the electricity meter, as part of the functions*1 are not supported.
However, this does not include UTY-VGGXs that are connected to a Group Remote Controller.
*1: [Electricity Apportionment Function] It is not possible to carry out apportionment processing for
indoor units such as Single split AC connected to Network converters.
The electricity cost for equipment connected to the network converter must be calculated in another
way.
[Energy Saving Function] The Target Electricity in the Peak Cut function is a target, and there are
no restrictions implemented for the Target Electricity.
V-II/V-III/VR-II/J-II/
J-IIS Series
Whm
Single split AC
Nests for other meters and multiple installations are not permitted.
The meter itself can be installed, but please only use one for the System Controller Lite power meter (if
you use both, the amount of electricity will be counted twice).
Ref. system 1
Whm
Ref. system 2
Ref. system 3
Whm
Copyright© 2013-2015 Fujitsu General Limited. All rights reserved.
V-II/V-III/VR-II/J-II/
J-IIS Series
Whm
Single split AC
Whm
292