Wiring Configuration: External Alarm Reset - Danfoss VLT FC 102 Operating Manual

Hvac drive
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

VLT HVAC Drive FC 102
Operating Guide
Table 33: Start/Stop with Reversing and 4 Preset Speeds
Drive
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39

6.1.7 Wiring Configuration: External Alarm Reset

Table 34: External Alarm Reset
Drive
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
56 | Danfoss A/S © 2023.09
Parameters
Function
Parameter 5-10 Terminal 18 Digital Input
Parameter 5-11 Terminal 19 Digital Input
Parameter 5-12 Terminal 27 Digital Input
Parameter 5-14 Terminal 32 Digital Input
Parameter 5-15 Terminal 33 Digital Input
Parameter 3-10 Preset Reference
Preset ref. 0
Preset ref. 1
Preset ref. 2
Preset ref. 3
*=Default value
Notes/comments:
D IN 37 is an option.
Parameter
Function
Parameter 5-11 Terminal 19 Digital Input
*=Default value
Notes/comments:
D IN 37 is an option.
Basic I/O Configuration
Setting
[8] Start
[10] Reversing*
[0] No operation
[16] Preset ref bit 0
[17] Preset ref bit 1
25%
50%
75%
100%
Setting
[1] Reset
AQ267037536117en-000101 / 130R0083

Advertisement

Table of Contents
loading