VLT HVAC Drive FC 102
Operating Guide
Table 58: 525–600 V, Enclosure Sizes A, B, and C
Enclosure
Power [kW (hp)]
A3
5.5 (7.5)
7.5 (10)
A5
1.1 (1.5)
7.5 (10)
B1
11 (15)
15 (20)
18.5 (25)
B2
22 (30)
30 (40)
B3
11 (15)
15–18.5 (20–25)
B4
22 (30)
30 (40)
37 (50)
C1
37 (50)
45 (60)
55 (60)
C2
75–90 (100–125)
C3
45 (60)
55 (75)
C4
75 (100)
90 (125)
Table 59: 525–690 V, Enclosure Sizes A, B, and C
Enclosure
Power [kW (hp)]
A3
1.1 (1.5)
1.5 (2.0)
2.2 (3.0)
3.0 (4.0)
4.0 (5.0)
5.5 (7.5)
7.5 (10)
104 | Danfoss A/S © 2023.09
Recommended
Recommended
fuse size
maximum fuse
gG-10
gG-32
gG-16
gG-10
gG-32
gG-16
gG-25
gG-80
gG-32
gG-40
gG-50
gG-100
gG-63
gG-25
gG-63
gG-32
gG-40
gG-125
gG-50
gG-63
gG-63
gG-160
gG-100
aR-160
aR-250
aR-200
aR-250
gG-63
gG-150
gG-100
aR-160
aR-250
aR-200
Recommended fuse
Recommended maxi-
size
mum fuse
gG-6
gG-25
gG-6
gG-25
gG-6
gG-25
gG-10
gG-25
gG-10
gG-25
gG-16
gG-25
gG-16
gG-25
Recommended circuit break-
er Moeller
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
NZMB2-A200
NZMB2-A250
Recommended circuit
breaker Moeller
PKZM0-16
AQ267037536117en-000101 / 130R0083
Specifications
Maximum trip
level [A]
25
25
63
100
50
100
160
250
150
250
Maximum trip lev-
el [A]
16
Need help?
Do you have a question about the VLT FC 102 and is the answer not in the manual?
Questions and answers