Typ EP 501
Auxiliary functions
24.2.3. DIR.CMD – Sense of effective direction of the positioner
set-point value
Use this auxiliary function to set the sense of effective direction between the input signal (INPUT) and the nominal
position (CMD) of the actuator.
Each auxiliary function, which is to be set, must be incorporated initially into the main menu (MAIN).
See Chapter "24.1. Activating and deactivating auxiliary functions".
Factory setting: Rise
DIR.CMD
ENTER
EXIT
Figure 48:
Operating structure DIR.CMD
The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key
symbol is indicated
Nominal position
(CMD)
Figure 49:
Graph - DIR.CMD
Rise
SELEC
Fall
on the display.
Input signal
(INPUT)
Direct effective direction
(e.g. 4 mA or 0 V → 0 %,
20 mA or 5/10 V → 100 %)
Inverse effective direction
(e.g. 4 mA or 0 V → 100 %,
20 mA or 5/10 V → 0 %)
EXIT
. During the save process, the save
english
95