23.5.3. Starting the function P.TUNE
WARNING!
Risk.of.injury.from.uncontrolled.process.
While the P.TUNE function is running, the control valve automatically changes the current degree of opening
and intervenes in the running process.
▶ Using suitable measures, prevent the permitted process limits from being exceeded.
For example by:
- an automatic emergency shutdown
- stopping the P.TUNE function by pressing the STOP key (press left or right key).
Procedure:
Key
Action
MENU
Press
/
Select P.TUNE
RUN
Hold down
as long as countdown (5 ...)
is running
Press any key
EXIT
Press
Table 42:
Automatic adjustment of X.TUNE
To stop P.TUNE, press the left or right selection key
The changed data is saved in the memory (EEPROM) only when there is a switch to the process level,
by leaving the main menu (MAIN) using the left selection key
symbol is indicated
Possible.error.messages.when.running P.TUNE:
Display
TUNE
err/break
P.TUNE
ERROR 1
Table 43:
P.TUNE; possible error messages
After making all the settings described in Chapter "Start-Up", the process controller is ready for use.
Activation and configuration of auxiliary functions is described in the following Chapter "24. Configuring the aux-
iliary functions".
84
Description
for approx. 3 s Switching from process level
During the automatic adjustment the following messages are indicated on
the display.
"starting process tune" - Start self-optimization.
"identifying control process" - Process identification. Typical process
variables are determined from the response signal to a defined stimulus.
"calculating PID parameters" - Structure and parameters of the process
controller are determined.
"TUNE ready" - Self-optimization was successfully completed.
Return to the main menu (MAIN).
Switching from setting level
on the display.
Cause of fault
Manual termination of self-optimization by
pressing the
EXIT
key.
No supply pressure connected.
No change to process variable.
english
Typ EP 501
Start-Up
setting level
process level.
STOP
.
EXIT
. During the save process, the save
Remedial action
Connect supply pressure.
Check process and, if required, switch on
pump or open the shut-off valve.
Check process sensor.