Basic.setting.of.the.process.controller; Basic.setting.of.the.process.controller; P.control -.Setting.up.and.parameterization.of.the.process.controller - EBRO ARMATUREN EP 501 C Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

Typ EP 501
Start-Up
23.
BASIC SETTING OF THE PROCESS
CONTROLLER
23.1.
P.CONTROL – Setting up and parameterization of
the process controller
To start up the process controller, you must make the following settings in the P.CONTROL menu:
1.
SETUP
Set up the process controller (configuration)
2.
PID.PARAMETER
Parameterize process controller
Operating structure:
P.CONTROL
ENTER
* The SP SCALE function is indicated only if the external set-point value default (external) menu option is activated under
SP INPUT.
Figure 25:
Operating structure P.CONTROL
Key:.
Insensitivity range (dead band) of the PID process controller
..Amplification factor of the process controller
..Reset time
..Hold-back time
..Operating point
..Filtering of the process actual value input
..Indication of the signal type for process actual value (4 - 20 mA, frequency input, Pt 100 input)
..Specification of the physical unit and scaling of the process actual value
..Type of set-point value default (intern or extern)
..Scaling of the process set-point value (only for external set-point value default)
..Enables a smooth switchover between AUTOMATIC and MANUAL mode
PID.PARAMETER
SETUP
EXIT
ENTER
DBND 0.1 %
KP
TN
TV
X0
FILTER
EXIT
ENTER
PV-INPUT
PV SCALE
SP-INPUT
SP-SCALE*
P.CO-INIT
EXIT
english
0.00
0.5
0.0
0.0 %
0
67