24.3.
Manual configuration of X.TUNE
This.function.is.needed.for.special.requirements.only..
For standard applications the X.TUNE function has been preset at the factory.
See chapter "21.2. X.TUNE – Automatic adjustment of the positioner".
For special requirements the X.TUNE function, as described below, can be manually configured.
Opening.the.menu.for.the.manual.configuration.of.X.TUNE
Key
Action
MENU
Press
/
Select X.TUNE
RUN
Briefly press
X.TUNE; opening the menu for the manual configuration of X.TUNE
X.TUNE
RUN
press.
briefly
EXIT
Figure 90:
Operating structure for the manual configuration of X.TUNE
150
Description
Switching from process level
for approx. 3 s
Opening the Manual.TUNE menu. The menu options for the manual
configuration of X.TUNE are displayed.
X.TUNE.CONFIG
X.TUNE.POS
X.TUNE.PWM
X.TUNE.AIR
english
Selecting.functions.for.X.TUNE
X.TUNE.DBDx
ENTER
X.TUNE.PARAx
X.TUNE.LEAKAGE
X.TUNE.Ypwm
X.TUNE.Yfric
EXIT
Determining.end.positions
ACT.limit
ENTER
ACT.nolimit
EXIT
Optimizing.PWM.signals
ENTER
yB.min
yE.min
EXIT
Determining.opening.and.closing.times
RUN
Hold down
as long as countdown (5 ...) is running
Typ EP 501
Auxiliary functions
setting level.
SELEC
Dead band
Control parameter
positioner
Leakage test
Parameter PWM
signals
Friction behavior
SELEC
Input values
POS.pMIN
POS.pMAX
EXIT
ENTER
Acknowledge
value
ENTER
Values are
displayed
INPUT
INPUT
OK
OK