Filter - Filtering Of The Process Actual Value Input - EBRO ARMATUREN EP 501 C Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

23.3.7.
FILTER – Filtering of the process actual value input
The filter is valid for all process actual value types and has a low pass behavior (PT1).
Factory setting: 0
Operating structure:
PID.PARAMETER
Figure 39:
Operating structure FILTER; filtering of the process actual value input
Setting.the.filter.effect.in.10.stages
Setting
0
1
2
3
4
5
6
7
8
9
Table 37:
Setting the filter effect
80
DBND 1.0 %
ENTER
FILTER
EXIT
Corresponds to cut-off frequency (Hz)
On page 204 you will find a table for entering your set parameters.
english
0
INPUT
Input value
Adjustment range: 0 ... 9
10
5
2
1
0.5
0.2
0.1
0.07
0.05
0.03
Typ EP 501
Start-Up
OK
ESC
Effect
Lowest filter effect
Largest filter effect

Advertisement

Table of Contents
loading

Related Products for EBRO ARMATUREN EP 501 C

This manual is also suitable for:

Ep 501Ep 501 l

Table of Contents