Error Messages While The P.q'lin Function Is Running; Error Messages While The P.tune Function Is Running - EBRO ARMATUREN EP 501 C Operating Instructions Manual

Electropneumatic positioner and process controller
Table of Contents

Advertisement

30.1.3. Error messages while the P.Q'LIN function is running

Display
Q.LIN
err/break
P.Q'LIN
ERROR 1
P.Q'LIN
ERROR 2
Table 101:
Error message on P.Q.'LIN; process controller Type EP 501 C

30.1.4. Error messages while the P.TUNE function is running

Display
TUNE
err/break
P.TUNE
ERROR 1
Table 102:
Error message on P.TUNE; process controller Type EP 501 C
186
Cause of fault
Manual termination of linearization by
pressing the
EXIT
key.
No supply pressure connected.
No change to process variable.
Failure of the supply pressure while
P.Q'LIN running.
Automatic adjustment of the X.TUNE
positioner not run.
Cause of fault
Manual termination of self-optimization by
pressing the
key.
EXIT
No supply pressure connected.
No change to process variable.
english
Typ EP 501
Maintenance and Troubleshooting
Remedial action
Connect supply pressure.
Check process and, if required, switch on
pump or open the shut-off valve.
Check process sensor.
Check supply pressure.
Run X.TUNE.
Remedial action
Connect supply pressure.
Check process and, if required, switch on
pump or open the shut-off valve.
Check process sensor.

Advertisement

Table of Contents
loading

Related Products for EBRO ARMATUREN EP 501 C

This manual is also suitable for:

Ep 501Ep 501 l

Table of Contents