Typ EP 501
Start-Up
23.2.
SETUP – Setting up the process controller
These functions specify the type of control.
The procedure is described in the following Chapters "23.2.1" to "23.2.5".
23.2.1.
PV-INPUT – Specifying signal type for the process actual
value
One of the following signal types can be selected for the process actual value:
• Standard signal
• Frequency signal
• Circuit with Pt 100
Factory setting: 4 ... 20 mA
When the operating voltage has been switched on, the device looks for connected sensor types
(automatic sensor detection).
When a sensor type (PT 100 or 4 ... 20 mA) is detected, the signal type is automatically implemented in the
PV-INPUT operating menu.
If no sensor signal is detected, the last setting is retained.
The signal type frequency signal cannot be detected automatically, but must be set manually in the
PV-INPUT menu.
Operating structure:
PV-INPUT
ENTER
EXIT
Figure 26:
Operating structure PV-INPUT
Specifying.signal.type.in.the.menu.SETUP.→.PV-INPUT:
Key
Action
Select PV-INPUT
/
ENTER
Press
/
Select signal type
SELEC
Press
EXIT
Press
Table 30:
PV-INPUT; Specifying signal type
4 ... 20 mA
flow rate, pressure, level
0 ... 1000 Hz
flow rate
-20 °C ... +220 °C
temperature
SELEC
Standard signal 4–20 mA
4-20 mA
(flow rate, pressure, level)
Frequency signal 0 ... 1000 Hz
Frequenz
(flow rate)
Circuit with Pt 100
PT 100
(temperature) -20 °C ... +220 °C
Description
The signal types are displayed.
The selected signal type is now marked by a filled circle
Return to SETUP.
.