4.5.5

AMAX-5018 Object Dictionary

4.5.5.1
Input Data
Table 4.32: Analog Input (0x6000 - 0x6FFF)
Index (hex)
Name
0x60n0:01
Aln_BurnOut
0x60n0:02
Aln_OverRange Over range detection
Aln_Under-
0x60n0:03
Range
0x60n0:11
Aln_Raw
0x60n0:13
Aln_Scale
n: Range from 0 to 5 refer to Ch.0 to Ch.5.
[1]: Burnout Detection can be used when the AIn_EnBurnOut (0x80n0:01) is
enabled, this function is only available for thermocouple input.
[2]: Over or Under range detections are only available for thermocouple input, the
alarm trigger value shows in the next table "Thermocouple Alarm Trigger Over/
Under Temperature and Accuracy".
Table 4.33: Thermocouple Alarm Trigger Over/Under Temperature and
Accuracy
Type
Type Range
J
0~760°C
K
0~1370°C
T
-100~400°C
E
0~1000°C
R
500~1750°C
S
500~1750°C
B
500~1800°C
-200~0°C
N
0~1300°C
AMAX-5000 Series User Manual
Meaning
[1]
Burnout detection
[2]
Under range detection
[2]
Analog input value (raw
data)
Analog input value
(scale data)
Under Temperature
Over Temperature
Alarm
Alarm
-80°C
840°C
-100°C
1370°C
-140°C
400°C
-100°C
1000°C
320°C
1760°C
320°C
1760°C
320°C
1820°C
-270°C
1300°C
-270°C
1300°C
68
Data type Flags Default value
BOOL
RO
0x00
BOOL
RO
0x00
BOOL
RO
0x00
UINT
RO
0x0000
DINT
RO
0x0000 0000
Accuracy
± 1.5°C
± 1.5°C
± 1.5°C
± 1.5°C
± 2.5°C
± 2.5°C
± 3.0°C
± 8.0°C
± 1.5°C