Amax-5017C Object Dictionary - Advantech AMAX-5000 Series User Manual

Ethercat slice i/o modules
Hide thumbs Also See for AMAX-5000 Series:
Table of Contents

Advertisement

4.2.5

AMAX-5017C Object Dictionary

4.2.5.1
Input Data
Table 4.12: Input Data (0x6000:01 – 0x6050:11)
Index (hex) Name
0x60n0:01 Aln_BurnOut
0x60n0:02 Aln_OverRange
0x60n0:03 Aln_UnderRange
0x60n0:11
Aln
n: Range from 0 to 5 refer to Ch.0 to Ch.5.
Converting current input value:
For the range 4~20 mA:
For the range ± 20 mA:
For the range 0~20 mA:
4.2.5.2
Burnout Detection Configuration
Table 4.13: Burnout Detection Configuration (0x8000:01 – 0x8050:14)
Index (hex) Name
0x80n0:01 AIn_EnBurnOut
0x80n0:11
AIn_Range
AIn_BurnOut-
0x80n0:14
Value
n: Range from 0 to 5 refer to Ch.0 to Ch.5.
[1]: Input current alarm function only available for current range in 4~20mA. Please
refer to the next table "Input Current Alarm Status".
AMAX-5000 Series User Manual
Meaning
Burnout detection
0: Disable
1: Enable
Over range detection
0: Disable
1: Enable
Under range detection
0: Disable
1: Enable
Read current input value UINT
= (
× 16
) + 4
65536
= (
× 40
)
20
65536
=
× 20
65536
Meaning
Enable burnout detection
0: Disable
1: Enable
[1]
Input range type
0x0180: 4~20mA
0x0181: ± 20mA
0x0182: 0~20mA
Burnout value
0: Output 0 (up scale)
1: Output 65535 (down
scale)
48
Data type Flags Default value
BOOL
RO
0x00
BOOL
RO
0x00
BOOL
RO
0x00
RO
0x0000
Data type Flags Default value
BOOL
RW
0x01
UINT
RW
0x0180
UINT
RW
0x0001

Advertisement

Table of Contents
loading

Table of Contents