2.6

Electromagnetic Protection

2.6.1

Cable Separation

In order to prevent electromagnetic disturbances to corrupt the signals and therefore
affect communication performances, network planning should always guarantee a
suitable separation of communication cables from other cable types, and especially
from power cables like supply lines or motor connections. This is shown in Figure
2.12
Figure 2.12 Minimum distance between communication and power cables.
In order to improve the immunity to electromagnetic disturbances and to reduce the
minimum permissible distance from power lines, EtherCAT cables can be routed
through metallic enclosures or conduits as shown in Figure 2-10.
Figure 2.13 Minimum distance with metallic separation conduits.
Table 2.2 lists the recommended minimum distance between communication cables
and power cables.
Table 2.2: Recommended Minimum Distance Between Communication
and Power Cables
Cable Separation Type
Without metallic separation
Open metallic cable conduit
Perforated metal plate conduit
Bulky cable conduit
AMAX-5000 Series User Manual
Minimum Distance
10 mm
8 mm
5 mm
0 mm
12