Amax-5001 Object Dictionary - Advantech AMAX-5000 Series User Manual

Ethercat slice i/o modules
Hide thumbs Also See for AMAX-5000 Series:
Table of Contents

Advertisement

3.1.6

AMAX-5001 Object Dictionary

3.1.6.1
Input Data
Table 3.4: Input Data (0x6000:01 - 0x6000:11)
Index (hex)
Name
0x6000:01
Over_Voltage_1
0x6000:02
Under_Voltage_1
0x6000:03
Over_Voltage_2
0x6000:04
Under_Voltage_2
0x6000:05
Over_Current
0x6000:06
DI0
0x6000:07
DI1
0x6000:08
DI2
0x6000:09
DI3
0x6000:11
Voltage_1
0x6000:12
Voltage_2
0x6000:13
Current
3.1.6.2
Module Configuration
Table 3.5: Module Configuration (0xF600:01 - 0xF600:10)
Index (hex)
Name
0xF600:01
Locate Module
0xF600:10
LED_Trigger
AMAX-5000 Series User Manual
Meaning
Voltage 1 > 28.8V
(24V*1.2)
Voltage 1 < 19.2V
(24V*0.8)
Voltage 2 > 28.8V
(24V*1.2)
Voltage 2 < 19.2V
(24V*0.8)
Bus current > 2A
Digital input channel 0
Digital input channel 1
Digital input channel 2
Digital input channel 3
Input voltage 1
Input voltage 2
Input current
Meaning
Data type Flags
Locate LED control
0: Turn Off
BOOL
1: Turn On
For RMA centre testing BOOL
24
Data
Flags Default value
type
UINT
RO
0x0000
UINT
RO
0x0000
UINT
RO
0x0000
UINT
RO
0x0000
UINT
RO
0x0000
UINT
RO
0x0000
UINT
RO
0x0000
UINT
RO
0x0000
UINT
RO
0x0000
REAL RO
Dec 0
REAL RO
Dec 0
REAL RO
Dec 0
Default value
RW
0x00
RW
0x00

Advertisement