Status Led (Only Push-Button Plus 55); Led Basic Setting; Led Orientation Light - MDT Push Button 55 Technical Manual

Hide thumbs Also See for Push Button 55:
Table of Contents

Advertisement

Technical Manual
Push-button 55 / Plus 55 [BE-TA55xx.x2]
4.4 Status LED
(only Push-button Plus 55)
Depending on the device, up to 8 status LEDs (one LED per button) can be configured. In addition, an extra
LED can be configured as an "orientation light" for each device.

4.4.1 LED basic setting

The LED basic settings affect all active status LEDs. The following table shows all available settings:
ETS Text

LED orientation light

Lock object for LEDs
Behaviour of the LEDs on
bus power return
Table 33: Settings – LED basic settings
4.4.1.1 LED Orientation light
The LED is located in the centre of the upper part of the button. When activated, the LED always lights up
green.
There are 4 selection options for the control. On the one hand, the LED can be switched permanently
"OFF". This deactivates the LED and it has no further function.
If the LED is to be used as an orientation light, for example, the LED can be switched on permanently via
the "ON" setting. Furthermore, the LED can be controlled via an external object. In this case, the polarity
for switch-on/switch-off can also be set.
When controlling via an external object, an additional communication object is displayed, which can then
be linked with any other 1 Bit communication object.
The following table shows the available communication objects:
Number
Name / Object function
* 49/69/89/109
LED Orientation light – Switch
Table 34: Communication objects – Orientation light
* Object numbers depend on the device version (number of buttons).
MDT technologies GmbH · Papiermühle 1 · 51766 Engelskirchen · Germany
Phone +49 (0) 2263 880 · knx@mdt.de · www.mdt.de
Dynamic range
[Default value]
OFF
ON
via external object:
0 = OFF / 1 = ON
via external object:
0 = ON / 1 = OFF
not active
active
do not request LED objects
request LED objects
Comment
Setting the control or functionality of
the orientation LED.
Activates a lock object which can
disable (= switch OFF) all LEDs..
Applies only to status LEDs 1 - 8
Setting whether to actively request
the objects after a reset.
Only active when "LED reacts to
external object".
Length
Usage
1 Bit
Switching the LED
38 / 49

Advertisement

Table of Contents
loading

Table of Contents