Command Menu/Time Clock
2. Set time and date
HH:MM WKD YYYY-MM-DD
00:00 MON 2000-01-01
Command Menu/Time Clock
2. Compensation
HH:MM WKD YYYY-MM-DD
00:00 MON 2000-01-01
When value is entered the following message
will appear
Daily Compen. (Sec):
Panel Config Updated
Default
00:00 MON 2000-01-01
Default: 0 seconds (no
compensation)
Compensation values
can range from -15 to
+15 seconds.
Use this function to set the time and date. Use
the "LEFT" and "RIGHT" keys to move the
cursor to the desired location in the display and
use the "UP" and "DOWN" keys to increase or
decrease the values. Press the "ENTER" key to
accept the changes and the "CANCEL" key to
ignore the changes.
Note: time is in 24hr format
Use the up down arrow keys to select daily
compensation value and press ENTER. For a
fast clock adjust negatively. For a slow clock
adjust positively. For example: for a clock which
runs 5 minutes a month (based on 30 days) fast
select -10 seconds.