Command Menu-->Panel Config-->Features
1. Manual Sig. Silence
Man. S i g. S i l.
[X ] EN AB LE
Command Menu-->Panel Config-->Features
2. Wtr/Sprk. Retd
W a t e r f lo w/S p r k R e t d
[X ] D I S AB LE
Command Menu-->Panel Config-->Features
3. Aux Dis Corr
Au x D i s. D i s C o rr
[X ] EN AB LE
Command Menu-->Panel Config-->Features
4. Sig-Sil Inh Tmr
S i g - S i l . I n h i b i t T i me r
[X ] D I S AB LE
Command Menu-->Panel Config-->Features
5. Aux. Dis. Dis Alam&Sv
Aux Dis. Dis Alm&Sv
[X ] D I S AB LE
Command Menu-->Panel Config-->Features
6. Auto Sig-Sil. Tmr
Au to S i g-S i l. Tm r
[X ] D I S AB LE
Command Menu-->Panel Config-->Features
7. Rem. Annun.
N o. o f R e m o t e A n n u n.
[X ] N ON E
Command Menu-->Panel Config-->Features
8. Alarm Xmit-Sil.
Al m Xm i t- S i l.
[X ] D I S AB LE
50
[X] ENABLE ->Default
[ ] DISABLE
[ ] ENABLE
[X] DISABLE->Default
[X] ENABLE ->Default
[ ] DISABLE
[X] DISABLE->Default
[ ] 10sec
[ ] 20sec
[ ] 30sec
[ ] 1min
[ ] ENABLE
[X] DISABLE->Default
[X] DISABLE->Default
[ ] 5 Min
[ ] 10 Min
[ ] 20 Min
[ ] 30 Min
[X] NONE->Default
[ ] 1
[ ] 2
...
[ ] 6
[ ] ENABLE
[X] DISABLE->Default
Use this function to enable or
disable the Signal Silence operation
on the panel.
By default all the Initiating Device
Circuits configured as waterflow or
sprinkler act as non-verified alarms.
If enabled, a retard operation is
performed for Initiating Device
Circuits configured as waterflow or
sprinkler. The maximum retard may
not exceed 90 seconds for Canada.
By default this function will
disconnect the auxiliary alarm relay
when the aux disconnect button is
pressed. If enabled, this function will
disconnect the auxiliary alarm relay
and all correlated relays when the
aux disconnect button is pressed.
Correlated relays include: RM-306
and SRM-312W.
Use this function to inhibit the signal
silence switch for a desired length of
time. The time period should expire
before the signals may be silenced.
According to the Canadian National
Building Code, this timer should be
set to one minute.
If enabled the Common Alarm and
Common Supervisory relays will be
disconnected when Aux. Disconnect
is pressed. If disabled, the Aux
disconnect switch has no effect on
the Common Alarm relay, the
Common Supervisory relay.
Use this function to set the time
period for which the Notification
Appliance Circuits will sound before
they are automatically silenced.
Use this function to program the
number of remote annunciators. Any
combination of remote annunciators
or smart relays can be used as long
as the number does not exceed 6.
The annunciators' addresses should
be linear: without gaps and in
sequence.
Use this function to allow the alarm
transmit and auxiliary alarm relay to
reset on the Signal Silence rather
than the Reset switch.