Introduction; Panel Type; Overall Features - Mircom FR-320 Series Installation And Operation Manual

Pre-action/deluge and agent release control panel
Hide thumbs Also See for FR-320 Series:
Table of Contents

Advertisement

1.0

Introduction

Mircom's FR-320 Series Pre-Action/Deluge and Agent Release Control Panel performs the
function of fire suppression in a wide variety of applications. It is capable of being used in an
agent release sprinkler system or in a pre-action or deluge sprinkler system. It can be used in
single-hazard or dual-hazard applications with or without cross-zoning. The panel includes
common alarm, supervisory, and trouble relays, and provides regulated and unregulated
auxiliary power along with four-wire smoke power. It supports auxiliary relays. The auxiliary
relays are based on a hazard area status. The FR-320 Series has six input zones and four
output zones, allowing for flexibility in most single and dual-hazard applications for both
deluge and agent releasing applications.
1.1

Panel Type

The panel can function as an agent release panel or as a pre-action/deluge panel, depending
on which of the available fixed configurations are chosen from the main programming menu.
1.1.1
Deluge sprinkler system
In deluge sprinkler systems open-valve sprinkler heads terminate to a water supply that is
controlled by a single valve. When the system detects fire, it automatically opens the valve via
a releasing circuit, allowing the water to flow through all the sprinkler heads. Deluge sprinkler
systems are useful for applications in which simultaneous discharge of water through every
sprinkler is required.
1.1.2
Pre-action sprinkler system
In a pre-action sprinkler system close-valve sprinkler heads are connected to pipes that are
supervised for air pressure. The pipes terminate directly to a water supply. Pre-action systems
are useful for applications in which the prevention of an accidental discharge of water is
required.
1.1.3
Agent release system
In an agent release system, an extinguishing agent (such as Argon, dry chemical, CO
etc.) is automatically released upon fire detection. An abort function is added to prevent the
false release of the extinguishing agent.
1.2

Overall Features

6 class B Initiating Device Circuits, which may be configured as class A using input class
A converter adder modules. Each Initiating Device Circuit is pre-configured as Alarm,
Supervisory (Latching or non-latching), water-flow, Manual Release Switch, or Abort
Switch. There are two LEDs per circuit, one for Trouble (amber), and one dual color
(amber/red) LED for Supervisory (amber) and Alarm (red).
4 power limited class B output circuits. Output circuits 1 & 2 are Notification Appliance
Circuits while output circuits 3 & 4 are releasing circuits (circuit 4 can work as a
Notification Appliance Circuit in some situations; check Pre-Programmed Modes on
page 62 for details). Each Notification Appliance Circuit process type is pre-configured
and can be silenceable. The signal rates depend on the selected pre-programmed
configuration.
A pushbutton associated with each Initiating Device Circuit and Notification Appliance
Circuit can individually disconnect (bypass) the circuit.
Configurable Signal Silence Inhibit and Auto Signal Silence Timers.
8
2
, Halon,