11.4
Mode 4: Agent Release, Dual Hazard, Not Cross-zoned, Split
Release
!
Attention: Dual hazard operation is not permissible for UL/ULC operation.
Out1
Signal
Steady
Out2
Signal
Escalating
Out3
Rel.
Releasing
Out4
Rel.
Releasing
RLS TMR 1 Started
RLS Tmr 1 Interrupted
RLS Tmr 1 Cancelled
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled
11.4.1 Zone Configuration
•
Detection Zone -1: Alarm (Hazard Area 1, not cross-zoned)
•
Detection Zone -2: Alarm (Hazard Area 1, not cross-zoned)
•
Detection Zone -3: Alarm (Hazard Area 2, not cross-zoned)
•
Detection Zone -4: Alarm (Hazard Area 2, not cross-zoned)
•
Detection Zone -5: Abort/Manual Release Combination (hazard 1)
•
Detection Zone -6: Abort/Manual Release Combination (hazard 2)
•
NAC -1: Escalating Signal, indicates Hazard Area 1 state
•
NAC -2: Escalating Signal, indicates Hazard Area 2 state
•
RAC -3: Releasing Circuit (Hazard Area 1)
•
RAC -4: Releasing Circuit (Hazard Area 2)
11.4.2 Hazard Configuration
•
Default Release Timer Value:
•
Default Manual Release Delay:
•
Default Abort Delay Type:
•
Default Soak Timer Value:
11.4.3 NAC Configuration
•
Default Escalating NAC code of Hazard Area State:
• Hazard Idle: Off
• Hazard Alarm: Temporal (see Table 9 and Table 10)
• Hazard Release: Steady
68
Detection Zones
Z1
Z2
Z3
Z4
Alm
Alm
Alm
Alm
X
X
X
X
X
X
X
X
Phantom Zones
Z5
Z6
Zp1
AB/MR
AB/MR
Z1+Z2
X
X
X
X
X
X
X
X
60 seconds
0 seconds
Standard UL
0 seconds
Release Timers
RT1
RT2
Zp2
Exp
Exp
Z3+Z4
X
X