Table 10 Settings Permitted in UL864
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED
PARTIES
This product incorporates field-programmable software. In order for the product to comply with the
requirements in UL864, Standard for Control Units and Accessories for Fire Alarm Systems, certain
programming features or options must be limited to specific values or not used at all as indicated below.
Program feature or
option
Temporal pattern in
conjunction with manual
alarm evacuation
control
Abort and manual
release on same circuit
(unsupervised)
Abort Delay Type (see
page 48)
Manual Signal Silence
(see page 50)
Signal Silence Inhibit
(see page 50)
Aux Disconnect
disconnects Common
Alarm and Common
Supervisory (see
page 50)
Alarm Transmit Silence
(see page 50)
Power Fail Timer (see
page 51)
Signal Isolators (see
page 51)
First Alarm NAC Code
(see page 51)
Second Alarm NAC
Code (see page 51)
Active EOL (see
page 52)
Configure the FR-320 Series Panels using the CFG-300 LCD Tool (see further documentation
packaged with CFG-300 for configuration information).
Permitted in UL864?
(Y/N)
Y
N
Y
Y
N
Y
Y
Y
Y
Y
Y
Y
Possible settings\methods
Modes 1, 2, 3, 4, 5, 6, 7, 8, 9,
10, 11, 12, 13, 14
Modes 1, 2, 3, 4, 5, 6, 7, 8, 9,
10, 11, 12, 13, 14
Standard UL, IRI, NYC, Local
Jurisdiction
Enabled, Disabled
Disabled, 10 seconds, 20
seconds, 30 seconds, 1
minute
Enabled, Disabled
Enabled, Disabled
None, 1 hour, 3 hours
Enabled, Disabled
Temporal, 20 BPM
Temporal, 60 BPM, 120 BPM
Enabled, Disabled
Settings permitted in
UL864
Mode 11
None
Standard UL
Enabled
Disabled
Disabled
Disabled
None
Disabled
Temporal
Temporal
Enabled if using an
active EOL resistor
ICAC-306
43