HUAWEI NetEngine 8000 F
Hardware Guide
Dust on devices may cause electrostatic discharge and result in poor contact for
connectors or metal connection points. This problem can shorten the life span of
devices and cause faults.
The equipment room must be free from explosive, conductive, magnetically-
permeable, and corrosive dust.
concentration in the equipment room.
Table 4-64 Requirements for dust particles in the equipment room
Mechanical active
material
Dust particle
Suspending dust
Precipitable dust
NOTE
Take the following measures to meet the requirements:
Requirements for Corrosive Gases
The room should be free from dusts and corrosive gases, such as SO
NH
Table 4-65 Requirements for corrosive gas concentration
Chemical
active material
SO
H
NO
Issue 05 (2023-03-31)
● Dust particle diameter ≥ 5 µm
● Suspending dust diameter ≤ 75 µm
● 75 µm ≤ precipitable dust diameter ≤ 150 µm
Use dustproof materials for ground, wall, and ceiling construction.
Use screens on the door and windows facing outside. The outer windows
should be dust-proof.
Clean the equipment room regularly and clean the air filter door monthly.
Wear shoe covers and ESD clothing before entering the equipment room.
.
Table 4-65
lists the requirements for the corrosive gas concentration.
3
Unit
mg/m
2
S
mg/m
2
mg/m
x
Copyright © Huawei Technologies Co., Ltd.
4 Hardware Installation and Parts Replacement
Table 4-64
lists the requirement for dust
Unit
3
Particle /m
3
mg/m
2
mg/m
·h
Concentration
≤0.30
3
≤0.10
3
≤0.50
3
Concentration
4
≤ 3x 10
(no visible dust
accumulated on a
workbench in three
days)
≤0.2
≤1.5
, H
S, and
2
2