Tab.42
Value of the
Description
Hybrid mode
(HP061) parame­
ter
Primary Energy
Optimisation of primary energy consumption: The control system chooses the generator that consumes the
least primary energy.
The switch between the heat pump and the boiler occurs at the value of the coefficient of performance
threshold COP Threshold(HP054) according to the primary energy consumption optimisation mode.
Hybrid Cost
Optimisation of energy costs for the consumer (factory setting): the control system chooses the cheapest
generator according to the coefficient of performance of the heat pump and according to energy cost.
The switch between the heat pump and the boiler occurs at the value of the threshold coefficient of per­
formance calculated according to energy cost optimisation mode with the energy cost parameters.
Peak elec. cost (HP062): Energy cost in Peak rate electricity cost (in cents)
Off-peak elec. cost (HP063): Energy cost in Off-peak electricity cost (in cents)
Gas or oil cost (HP064): Cost of fossil energy (oil or gas) – price per m
0.01 to 2.50 €/kWh
Hybrid CO2
Optimisation of CO
The switch between the heat pump and the boiler occurs at the value of the coefficient of performance
threshold calculated according to the optimisation mode for CO
No Hybrid
No optimisation: The heat pump always starts up first, regardless of the conditions. The boiler back-up
starts up afterwards, if necessary.
Tab.43
Access
Air Src Heat pump >
23.5
Parameters, counters,
signals > Parameters
Air Src Heat pump >
23.5
Parameters, counters,
signals > Adv. Parameters
CIRCA0,
CIRCA1,
21.7
19.8
CIRCB1, CIRCC1 >
Parameters, counters,
signals > Parameters
7756241 - v02 - 19062020
2. Choose the optimisation for energy consumption
emissions: The control system chooses the generator that emits the least CO
2
7.3.11
This function is only available when the Zone Function parameter is set to
Mixing Circuit or Fan Convector (Installation configuration menu >
CIRCA1, CIRCB1 or CIRCC1 > Circuit function).
1. Configure the following parameters:
On
Parameter
CH function on
(AP016)
Cooling mode
(AP028)
Floor Cool. setpoint
(CP270, CP271, CP273, CP274)
Fan Cool. setpoint
(CP280, CP281, CP283, CP284)
RevContactOTH cool
(CP690, CP691, CP693, CP694)
2. If necessary, force cooling or modify the cooling temperatures for the
2

Configuring underfloor cooling or a convection fan

Description
Enable central heating heat
demand processing
Configuration of the cooling
mode
Cooling flow temperature
setpoint for the underfloor
cooling
Cooling flow temperature
setpoint for the fan convector
Reversed OpenTherm
contact in cooling mode for
heat demand per zone
CIRCA0, CIRCA1, CIRCB1 or CIRCC1 circuits.
3
or per litre – Can be set from
emissions.
Adjustment required
Deactivating heating also de­
activates cooling.
On
Active cooling on
18 °C (default value).
Set the temperature accord­
ing to the type of floor and
the level of humidity.
7 °C(default value).
Set the temperature accord­
ing to the type of floor and
the level of humidity.
No
Yes
Check the setting according
to the thermostat or room
sensor used.
7 Settings
.
2
MIT-M
53