DeDietrich MIT-M /E Installation, User And Service Manual page 40

Reversible packaged air source heat pump
Table of Contents

Advertisement

5 Installation
Fig.32
3
2
4
MW-8800N003-6
Fig.33
2
1
Z
1/2 Z
1 Optimum location
2 Possible position
Fig.34
40
MIT-M
Plugs diameter 4 mm/drill diameter 6 mm
1. Choose a recommended location for the outdoor sensor.
2. Put the 2 plugs in place, delivered with the sensor.
3. Secure the sensor using the screws provided (diameter 4 mm).
4. Connect the cable to the outdoor temperature sensor.
Place the outside sensor in a position that covers the following
characteristics:
2
1
H
1/2 H (min. 2,5 m)
Avoid placing the outside sensor in a position with the following
characteristics:
Fitting the outdoor sensor
Recommended positions
On a façade of the area to be heated, on the north if possible.
Half way up the wall of the area to be heated.
Under the influence of changes in the weather.
Protected from direct sunlight.
Easy to access.
1/2 H (min. 2,5 m)
H
H Inhabited height controlled by the sensor
Z Inhabited area controlled by the sensor
Positions to be avoided
Masked by part of the building (balcony, roof, etc.).
Close to a disruptive heat source (sun, chimney, ventilation grid, etc.).
1
2
MW-8800N001-3
MW-3000014-2
7756241 - v02 - 19062020