7 Settings
Parameter
Description
Delay stop backup
Shutdown time delay for back-ups in central heating mode
CH (HP031)
Can be set from 0 Min to 600 Min
Delay Min.Outdoor
Start-up time delay for back-ups corresponding to the minimum outdoor tempera­
T. (HP047)
ture HP049. The dynamic time delay is activated when HP030=0
Can be set from 0 Min to 60 Min
Delay Max.Outdoor
Start-up time delay for back-ups corresponding to the maximum outdoor temper­
T (HP048)
ature HP050. The dynamic time delay is activated when HP030 = 0
Can be set from 0 Min 60 Min
Min.Outdoor
Minimum outdoor temperature used to set HP047.
T.backup (HP049)
Can be set from -30 °C to 0 °C
Max.Outdoor
Maximum outdoor temperature used to set HP048.
T.backup (HP050)
Can be set from -30 °C to 20 °C
Min. Outdoor T. HP
Minimum outdoor temperature authorising heat pump operation.
(HP051)
Can be set from -20 °C to 5 °C
Delay BackupStage
Time delay for activating the second electrical back-up stage in central heating
CH (HP108)
mode
Can be set from 1 Min to 255 Min
Min. water pressure
Appliance will report low water pressure below this value
(AP006)
Can be set from 0 bar to 6 bar
MessMinWaterPress
Warning message indicating that pressure is low
ure (AP058)
Can be set from 0 bar to 2 bar
Tab.84
Adv. Parameters menu
Parameter
Description of the advanced parameters
Max. HP Flow T.
Maximum flow temperature of the heat pump without backup energy sources.
(HP002)
Can be set from 20 °C to 65 °C
Min. HP Cooling T.
Minimum flow temperature of the heat pump in cooling mode
(HP003)
Can be set from 5 °C to 30 °C
Minimum flow rate
Minimum flow rate.
(HP010)
Can be set from 0 l/min to 90 l/min
Flow rate warning
Flow rate that triggers a warning message indicating that flow rate becomes
(HP011)
insufficient
Can be set from 0 l/min to 95 l/min
Backup type
Type of backup used in the heat pump:
(HP029)
0 =No Backup
1 =1 Electrical Stage
2 =2 Electrical Stages
3 =Boiler Backup
Elec. Pulse value
Value of the pulse coming from the electrical counter.
(HP033)
Can be set from 0 Wh to 1000 Wh
Backup 1 capacity
Declaration of the capacity of the 1st stage of the electrical backup used for the
(HP034)
energy counter.
Can be set from 0 kW to 10 kW
Value accepted when HP031 = 0
Backup 2 capacity
Declaration of the capacity of the 2nd stage of the electrical backup used for the
(HP035)
energy counter.
Can be set from 0 kW to 10 kW
Value accepted when HP031 = 0
COP Threshold
COP threshold above which the heat pump is authorised to operate.
(HP054)
Hybrid mode
Not used
(HP061)
Boiler efficiency
Not used
(HP068)
68
MIT-M
Factory setting
4
8
30
-10
15
-20
4
0.3
0.8
EHC–05 factory
setting
65
5
5 for 6 kW
8 for 8 kW
12 for 11 kW
7 for 6 kW
9 for 8 kW
14 for 11 kW
2
1
0
0
2.5
0
100