7 Settings
Tab.36
Access
DHW tank >
Parameters, counters,
signals > Parameters
Tab.37
Energy meter
Connections
Energy meter specifications
50
MIT-M
When discomfort is experienced in domestic hot water mode, the installer
may adjust the domestic hot water production setting parameters to
increase domestic hot water comfort, to the detriment of heating comfort.
1. Adjust the following parameters:
On
Parameter
Hysteresis DHW
(DP120)
Min. CH before DHW
(DP048)
Max. DHW duration (DP047)
7.3.8
Configure the back-up boiler according to its control panel. Set the installer
parameters.
1. Switch the boiler control system to 24h/24 comfort mode.
2. Heating set point temperature = Domestic hot water set point
7.3.9
The electrical energy meter is connected to the S0+/S0- input on the EHC–05 PCB.
Do not install meters for the electrical back-ups.
Minimum admissible voltage: 27 V
Minimum admissible intensity: 20 mA
Minimum pulse time: 25 ms
Maximum frequency: 20 Hz
Pulse weight: between 1 and 1000 Wh
If the meter impulse weight is given in number of impulses/kWh, the impulse weight must
be between the following numbers: 1, 2, 4, 5, 8, 10, 20, 25, 40, 50, 100, 125, 200, 250, 500
or 1000.
Energy metering provides information on:
electrical energy consumption,
the production of thermal energy for heating, domestic hot water and
cooling modes.
The thermal energy from the hydraulic or electrical back-up is
automatically factored in by the control system to provide the full tally of
restored thermal energy.
Important
The consumption of electricity may rise.
Description
Hysteresis temperature
relative to the DHW
temperature setpoint
Minimum heating duration
between two periods of
domestic hot water
production
Maximum duration of the
domestic hot water
production
Configuring a hydraulic back-up
temperature + 5°C.
See
Boiler installation manual.
Configuring the estimated electrical energy consumption
function
Adjustment required
Reduce the set point temper
ature differential triggering
the domestic hot water tank
to be charged.
Reduce the minimum heating
duration between two do
mestic hot water production
runs
Increase the maximum au
thorised duration for domes
tic hot water production
7756241 - v02 - 19062020