8 Connection and installation examples
Tab.103
Access
CIRCA0> Parameters,
21.7
counters, signals > Parameters
Tab.104
Access
CIRCB1 > Parameters,
19.8
counters, signals > Parameters
Tab.105
Access
DHW tank > Parameters,
counters, signals > Parameters
Tab.106
Access
Air Src Heat pump >
23.5
Parameters, counters, signals >
Adv. Parameters
82
MIT-M
4. Configure and check the parameters of the CIRCA0 circuit.
On
Parameter
MaxZoneTFlowSetpoint (CP000) Maximum Flow Temperature setpoint zone: 75 °C
Zone Function (CP020)
5. Set the heating curve on the CIRCA0 circuit to a gradient of 1.5. Adapt
the values of the heating curve in order to obtain optimum comfort.
6. Configure the parameters for the CIRCB1 circuit.
On
Parameter
MaxZoneTFlowSetpoint (CP000) Maximum Flow Temperature setpoint zone: 40 °C
Zone Function (CP020)
7. Set the heating curve on the CIRCB1 circuit with a gradient between
0.4 and 0.7. Adapt the values of the heating curve in order to obtain
optimum comfort.
8. Configure the parameters of the (DHW) domestic hot water tank.
On
Parameter
Max. DHW duration (DP047)
Maximum duration of the DHW
production
Min. CH before DHW (DP048)
Min. heating duration before
DHW prod.
DHW management (DP051)
Hysteresis DHW temperature
setpoint
(DP120)
9. Configure the heat pump parameters
On
Parameter
Cooling mode (AP028)
Adjustment required
Adjust the temperature as required
Functionality of the zone: Direct
Adjustment required
Adjust the temperature according to need
Functionality of the zone: Mixing Circuit
Adjustment required
3 hours
Adjust the duration according to need
2 hours
Adjust the duration according to need
ECO (Only HP)
15 °C
Adjust the temperature according to need
Adjustment required
Configuration of the cooling mode
Off
Active cooling on
Authorisation for cooling has been set.
7756241 - v02 - 19062020